54
UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
Figure 4-20. UPS ISBM section power terminal detail BB - separate battery
4.8.2 Battery wiring
CAUTION
When sizing the battery system, do not exceed the internal battery charger capabilities. See
Chapter 10: “Product specifications” for maximum battery charger current.
NOTE
An installed FI-UPM is always designated as UPM 4.
To install wiring to connections:
1.
Route the battery cables between the UPS ISBM section and the battery system or battery dis-
connect. See figure Figure 4-15 through Figure 4-20 and Figure 4-22 for wiring access information
and terminal locations.
2.
If wiring the UPS for a common battery, proceed to step 3; if wiring for a separate battery, proceed
to step 5.