![Eaton Powerware 9395 User And Installation Manual Download Page 145](http://html.mh-extra.com/html/eaton/powerware-9395/powerware-9395_user-and-installation-manual_525182145.webp)
1029052
UPS 675-1100 kVA 3..4x(225-275) kVA
137
Revision 008
User’s and Installation Guide
The Event History Log lists up to 500 system events in chronological order with the most recent event
listed last. In this mode, system events are continually logged through the serial port to the device
connected to the port.
The printed log entries contain a time and date stamp and the alarm text message. Terminal mode
uses this format for printing alarm entries:
MM DD YYYY HH:MM:SS.hh KYWD MESSAGE <CR> <LF>
An alarm message is prefixed by the word “CLEAR” whenever an alarm is entered into the Event
History Log with a cleared status.
If a port is operating in Terminal mode and is connected to a computer, you can press
[Esc] [H]
to print
the entire log with a firmware version header. The log in terminal mode is always in english.
MODEL: Eaton 9395
CTO: TF12710000000
SERIAL:
MCU DSP:70.81.14
MCU BOOTLOADER:80.40
MCU PLD:1.00
PMF 1 DSP:80.81.14
PMF 1 BOOTLOADER:80.40
PMF 1 PLD:1.00
XSLOT CAN BRIDGE:0.00
CSB DSP:70.81.14
CSB BOOTLOADER:1.12
DISPLAY:1.06
TIME: 19:17:16 DATE: 03/23/2099
03/16/2099 21:25:20.355 S138: CONTROL POWER ON (PM1)
03/16/2099 21:25:20.515 N011: OUTPUT UNDER OR OVER FREQ (PM1)
03/16/2099 21:25:20.675 S302: EEPS CONFIGURING (PM1)
03/16/2099 21:25:23.475 N267: POWER MODULE CABLE FAIL 15 (PM1)
03/16/2099 21:25:25.180 N271: DC HW AMPS LIMIT (PM1)
03/16/2099 21:25:25.215 N007: INPUT AC UNDER VOLTAGE (PM1)
Where
Equals
MM
Month (2 digits)
DD
Day (2 digits)
YYYY
Year (4 digits)
HH
Hour (2 digits)
MM
Minute (2 digits)
SS
Second (2 digits)
hh
Hundredths of Second (2 digits)
KYDW
Keyword (ALARM, NOTICE, COMMAND, or STATUS)
Message
System Diagnostic Information
<CR>
Carriage Return Character (ASCII 13)
<LF>
Line Feed (ASCII 10)