4
UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
uses these inputs to monitor the building alarms in addition to the UPS status. See Chapter 8:
“Communication” for additional information.
•
Alarm Contact – One alarm contact is provided for connection to equipment at the facility, such as
a light, an audible alarm, or a computer terminal. The equipment connected to this contact alerts
you to a UPS alarm. See Chapter 8: “Communication” for additional information.
•
X-Slot Communication Bay – A four-slot communication bay is provided as a standard feature. Four
optional X-Slot cards can be installed in the UPS module at any time. See Chapter 8:
“Communication” for additional information.
•
ConnectUPS -X Web/SNMP Card – This X-Slot card is provided as standard equipment and
provides remote monitoring through a Web browser interface, e-mail, and a network management
system (NMS) using SNMP. See Chapter 8: “Communication” for additional information.
1.1.4 Advanced Battery Management
A three-stage charging system increases battery service life by optimizing recharge time, and protects
batteries from damage due to high current charging and inverter ripple currents. Charging at high
currents can overheat and damage batteries.
1.1.5 Power Management Software
Eaton LanSafe® Power Management Software is bundled as part of the Software Suite CD shipped
with the UPS. See Chapter 8: “Communication” for additional information.
1.2 Options and accessories
Contact an Eaton sales representative for information about the following options.
1.2.1 Field Installed UPM
A Field Installed UPM (FI-UPM) provides N+1 redundancy for the UPS system. The FI-UPM may be
installed at any time in the future when power needs change. The module cabinet is installed on the
left side of the UPS and is wired directly to the UPS. No input or output wiring changes are needed for
redundancy. Operation remains the same as for the original UPS.
1.2.2 Maintenance Bypass Module
The Maintenance Bypass Module (MBM) enables power to completely bypass and isolate the UPS so
that the UPS can be safely serviced or replaced without interrupting power to critical systems.
1.2.3 Sync Control
An optional Eaton 9395 Sync Control maintains the critical load outputs of two separate single module
Eaton 9395 UPS systems in synchronization. This option facilitates the uninterrupted transfer of the
load from one load bus to another by means of a transfer switch. The Sync Control is housed in a wall-
mounted panel that can be located between the UPS units for easy wiring.