24
UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
Table 3-5: UPS cabinet power cable/busbar terminations for the Eaton 9395-825(675) and 9395-1100(900)
NOTE
Bypass terminations are not applicable to IOM configurations.
Table 3-6: Recommended installation parts (not supplied by Eaton Corporation)
External overcurrent protection is not provided by this product, but is required by codes. Refer to
Table 3-4 for wiring/busbar requirements. If an output lockable disconnect is required, it is to be
supplied by the user.
Terminal function
Terminal
Function
Tightening torque
Nm
Bolt size
AC input to UPS rectifier
E1
Phase L1
80 (47)
M12 (M10)
E2
Phase L2
80 (47)
M12 (M10)
E3
Phase L3
80 (47)
M12 (M10)
AC input to bypass
E6
Phase L1
80 (47)
M12 (M10)
E7
Phase L2
80 (47)
M12 (M10)
E8
Phase L3
80 (47)
M12 (M10)
AC output to critical load
E9
Phase L1
80 (47)
M12 (M10)
E10
Phase L2
80 (47)
M12 (M10)
E11
Phase L3
80 (47)
M12 (M10)
DC input from battery to UPS
E4
Battery (+)
80 (47)
M12 (M10)
E5
Battery (-)
80 (47)
M12 (M10)
Input and output neutral
E12
Neutral
80 (47)
M12 (M10)
Customer ground
Ground
Ground
80 (47)
M12 (M10)
Part
Size
Quantity
Manufacturer
Part
number
Notes
Bolt
M12 x 50 mm
As required
N/A
N/A
Quantity per lug
hole
Bolt
M10 x 50 mm
As required
N/A
N/A
Flat washer
M12
As required
N/A
N/A
Lock washer
M12
As required
N/A
N/A
Nut
M12
As required
N/A
N/A
UPS model
Input rating
Load rating
400 V
9395-675, 3*225
100%
1200 A
9395-825, 3*275
100%
1500 A
9395-900, 4*225
100%
1500 A
9395-1100, 4*275
100%
2000 A