UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
4.
On the Charger Control Command screen, select
CHARGER OFF
.
5.
Press the SELECT pushbutton on the Charger Command menu bar.
7.4.31 Using the UPS LOAD OFF pushbutton or command
A UPS Load Off is initiated by the LOAD OFF pushbutton from the main menu bar, the Load Off
command on the UPS Control Command screen, or Load Off command on the Bypass Control
Command screen. The UPS LOAD OFF controls the UPSs outputs by powering down the UPS and de-
energizing the critical load.
The UPSs (including Bypass) remain off until restarted.
NOTE
The UPS Load Off controls each UPS independently and does not shut down the whole
distributed bypass system unless all UPSs have been transferred to bypass. To immediately shut
down the whole system, use the REPO switch (see Section 7.4.32).
To use the LOAD OFF pushbutton:
1.
Press the LOAD OFF pushbutton on the UPS to shut down.
The Load Off screen is displayed, providing a choice to proceed or abort the shutdown.
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energize the critical load.
2.
To shut down the UPS, press LOAD OFF from the Load Off menu bar, and hold for three seconds.
To abort the shutdown, press CANCEL.
When LOAD OFF is selected and held for three seconds, the input, output, battery, and bypass
backfeed contactors open, and the power module is turned off on the UPS.
3.
If another UPS is to be shut down, proceed to that UPS and repeat Steps 1 and 2.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
4.
Restart the UPS after pressing the LOAD OFF pushbutton by following the procedure in Section
7.4.1 or Section 7.4.2 on page 118.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is
opened and the MOB is opened.
To use the LOAD OFF command:
1
Press the CONTROLS pushbutton on the main menu bar of the UPS to be shut down. The System