108
UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
5.
Press the SELECT pushbutton on the UPS Command menu bar.
The UPS starts High Alert mode with the UPMs online supplying the critical load. After one hour
the UPS transfers to Variable Module Management System mode.
The Online status indicator is illuminated. The UPS status indicates
HIGH ALERT
. The UPM status
indicates
ONLINE
. The power module is on.
7.3.8 Enable Variable Module Management System mode from the bypass
command menu
To enable Variable Module Management System mode:
NOTE
The Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually
exclusive. If the Energy Saver System mode is enabled, the Variable Module Management
System mode commands will not be displayed.
1.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the BYPASS command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command
screen is displayed.
4.
On the Bypass Control Command screen, select
ENABLE VAR MODULE MANAGEMENT
.
5.
Press the SELECT pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Variable Module Management System mode. In approxi-
mately twenty seconds the UPS calculates the required number of UPMs needed to support the
load.
The Online status indicator is illuminated. The UPS status indicates
VMMS
. The UPM sta-
tus indicates
ONLINE
.
7.3.9 Disable Variable Module Management System mode from the
bypass command menu
To disable Variable Module Management System mode:
NOTE
The Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually
exclusive. If the Energy Saver System mode is enabled, the Variable Module Management
System mode commands will not be displayed.
1.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the BYPASS command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command
screen is displayed.
4.
On the Bypass Control Command screen, select
DISABLE VAR MODULE MANAGEMENT
.