MAINTENANCE BYPASS
Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide
S
P-164000200 Rev 4
47
4.
Using the UPS LCD menu, force the UPS to Bypass
(Control > Go to bypass). The
indicator displays, indicating the
UPS is in bypass mode.
5.
If the 9PX PPDM voltage switch is set to 208V, confirm the UPS
output voltage through the front panel (refer to the UPS user's
guide).
6.
On the 9PX PPDM front cover, unsnap and remove the square
center cover.
7.
Turn the bypass switch on the 9PX PPDM to the UPS (normal)
position (see Figure 35).
208V
2
4
0V
NORMAL
BYPASS
Figure 35. Setting the Bypass Switch to UPS (Normal)
8.
Using the UPS LCD menu, force the UPS to Normal mode
(Control > Go back Normal). The
indicator remains on,
indicating that your equipment is now protected by the UPS.
9.
Reinstall the 9PX PPDM square center cover.