Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide
S
P-164000200 Rev 4
35
Chapter 6
Startup
This chapter provides instructions for starting up Eaton 9PX PowerPass
Distribution Modules (PPDMs) or 9PX Transformers with a 9PX
5000/6000/8000/11000 VA UPS. System configuration connection
diagrams are also provided.
Startup with the UPS
To start up a 9PX PPDM or 9PX Transformer with the UPS:
NOTE
If you are installing a remote power-off (RPO) switch, install the switch before
powering on the UPS. Refer to “RPO Installation” in the 9PX UPS user's guide for instructions.
NOTE
Refer to the 9PX UPS user's guide for recommended upstream protection. For
European models, also refer to the recommendations for downstream protection.
NOTE
Before startup, refer to the 9PX UPS/EBM/MBP user's guides for additional
configuration information.
NOTE
To change the UPS default settings, refer to “Display Functions” in the UPS user's
guide.
Refer to the UPS user's guide for UPS operation.
1.
Ensure that the upstream circuit breaker is OFF.
2.
Plug the input and output cords of the 9PX PPDM or 9PX
Transformer model into the input and output connectors on the
UPS (see “System Configuration Connections” on page 40 for
connection illustrations).
3.
Verify that the UPS internal battery connector is connected (refer to
the UPS/EBM user's guide).
4.
For 8k or 11k
EBM only.
Switch all battery circuit breakers to the
ON (
|
) position (refer to the UPS/EBM user's guide).
Summary of Contents for PowerPass 9PXPPDM1