4 Configuring the device
4.4 MODBUS register
NZM-XMC Measuring and Communication Module
11/16 MN01219001Z-EN
www.eaton.com
39
4.4.6.1 Overview of Modbus coils
4.4.6.2 Delete energy values (coil 2100)
This clears the counter for the power. The value is reset automatically to 0.
4.4.6.3 Delete maximum demand (coil 2101)
Initializes the maximum acceptance value and clears the previous value.
All the stored values used to calculate the maximum demand value will be
reset. To do this, registers 68 and 69 are set to a value of 0.
4.4.6.4 Delete maximum and minimum values (coil 2102)
This deletes the maximum and minimum values of each parameter.
The register is erased to 0 automatically.
4.4.6.5 Deleting power values (maximum/minimum, acceptance value) (coil 2103)
This setting corresponds to the sending of the three commands above.
The register is erased to 0 automatically.
The following actions are performed:
•
Energy values are deleted.
•
Max. demand is deleted.
•
Delete maximum and minimum value.
4.4.6.6 Delete maximum value of maximum demand (coil 2104)
Resets the maximum value of the maximum demand value. Registers 164
and 165 are set to a value of 0. The ongoing calculation will not change.
Variable
Coil
Part no.
Function
code
Digital outputs
1 -2
R/W
1; 5
Restart the whole device
1)
2000
W
5
Delete power values
2100
W
5
Initialize max. demand
2101
W
5
Delete maximum and minimum values
2102
W
5
Delete power (max./min., demand value)
2103
W
5
Delete maximum acceptance value
2104
W
5
1) = acceptance of a new configuration