7 Appendix
7.1 Technical data
NZM-XMC Measuring and Communication Module
11/16 MN01219001Z-EN
www.eaton.com
49
7 Appendix
7.1 Technical data
7.1.1 Basic devices
Unit
NZM…-XMC-S0
NZM…-XMC-MB(-250)
General
Dimensions
(W x H x D)
mm
209 x 132 x 91 (3 pole)
251 x 132 x 91 (4 pole)
NZM…XMC-MB
209 x 132 x 91 (3 pole)
251 x 132 x 91 (4 pole)
NZM…XMC-MB-250
125 x 132 x 87 (3 pole)
165 x 132 x 87 (4 pole)
Weight
g
850 (3 pole)
975 (4 pole)
NZM…XMC-MB
850 (3 pole)
975 (4 pole)
NZM…XMC-MB-250
750 (3 pole)
875 (4 pole)
Power supply
Voltage
V DC
24 ±10 %
24 ±10 %
Maximum current
mA
200
200
Conductor
Phoenix Contact GMVSTBR 2.5-2-ST-7.62
Phoenix Contact GMVSTBR 2.5-2-ST-7.62
Voltage measurement
Rated operating voltage
V AC
600
600
Maximum surge voltage 8/20
m
s
kV
8
8
Voltage range
V AC
72 - 600
72 - 600
Surge impedance (impedance)
k
Ω
1000
1000
Frequency
Hz
45 - 65
45 - 65
Accuracy
0.4 % measured value + 0.1 % FS
(full scale)
0.4 % measured value + 0.1 % FS
(full scale)
Category: EN 61010
CAT IV-600 V
CAT IV-600 V
Current measurement
Rated operational current
A AC
300 (300 A version)
500 (500 A version)
300 (300 A version)
500 (500 A version)
Current Range
A AC
1 - 350 (300 A version)
1 - 740 (500 A version)
1 - 350 (300 A version)
1 - 740 (500 A version)
Maximum current impulse for 1s
kA
30
30
Frequency Hz
45 - 200
45 - 200
Accuracy
0.45 % measured value + 0.05 % FS
(full scale)
0.45 % measured value + 0.05 % FS
(full scale)
Category: EN 61010
CAT IV-600 V
CAT IV-600 V