4 Configuring the device
4.2 MODBUS register
28
NZM-XMC Measuring and Communication Module
11/16 MN01219001Z-EN
www.eaton.com
4.2.6 Alarm setup
Up to six different alarm messages (load warnings) can be set. These can be
stored in six corresponding register ranges (
alarm settings for the maximum and minimum values, the release delay, the
monitored parameters and the output.
Table 10: Registers for alarm messages
No. of the
alarm
NZM-XMC-MB
register range
NZM-XMC-TC-MB
register range
1
1150 - 1155
1150 - 1155
2
1160 - 1165
1200 - 1205
3
1170 - 1175
4
1180 - 1185
5
1180 - 1195
6
1200 - 1205
Register
Variable
Value range
1150, 1151
Maximum value
Depends on parameter (default: 0)
1152, 1153
Minimum value
Depends on parameter (default: 0)
1154
Delay
0 - 9999 s (default: 0)
1155H
1)
Parameter code
1 - 48
1155L
2)
Out
0: Alarm disabled
1: Basic device output 1
2: Basic device output 2
3 - 6: Expansion card 1 outputs
7 - 10: Expansion card 2 outputs
(not in model NZM…-XMC-MB-250)
1) H = High byte
2) L = Low byte
→
To activate changes, write TRUE to coil 2000.