4 Configuring the device
4.4 MODBUS register
NZM-XMC Measuring and Communication Module
11/16 MN01219001Z-EN
www.eaton.com
35
4.4.2 Maximum and minimum electrical parameters
Registers 96 to 191 store the maximum values of each parameter (see
column “Maximum” in Table 9). Registers 192 to 287 likewise store analog
the minimum values recorded (see column “Minimum” in Table 9).
31
Active energy 3-phase
kWh
Active energy 3-phase
kWh
60
61
156
157
252
253
R
32
Inductive reactive energy
3-phase
kvarh
Inductive reactive energy
3-phase
kvarh
62
63
158
159
254
255
R
33
Capacitive reactive energy
3-phase
kvarh
Capacitive reactive energy
3-phase
kvarh
64
65
160
161
256
257
R
34
Apparent power
VA
Apparent power
VA
66
67
162
163
258
259
R
35
Max. Demand of parameter
defined in register 1250/
1251
W|VA|mA
Max. Demand of parameter
defined in register 1250/
1251
W|VA|mA
68
69
164
165
260
261
R
36
Consumed capacitive
reactive energy L2
kvarh
Averaged current, 3-phase
mA
70
71
166
167
262
263
R
37
Consumed capacitive
reactive energy L3
kvarh
Neutral current
mA
72
73
168
169
264
265
R
38
Apparent power L1
VA
Apparent power L1
VA
74
75
170
171
266
267
R
39
Apparent power L2
VA
Apparent power L2
VA
76
77
172
173
268
269
R
40
Apparent power L3
VA
Apparent power L3
VA
78
79
174
175
270
271
R
41
Built-in (no function)
–
Built-in (no function)
–
80
81
176
177
272
273
R
42
Max. demand value 2
–
Max. demand value 2
–
82
83
178
179
274
275
R
43
Max. demand value 3
–
Max. demand value 3
–
84
85
180
181
276
277
R
44
Apparent energy 3-phase
kVAh
Apparent energy 3-phase
VAh
86
87
182
183
278
279
R
45
Produced active energy
3-phase
kWh
Produced active energy
3-phase
kWh
88
89
184
185
280
281
R
46
Produced inductive reactive
energy 3 phase
kvarh
Produced inductive reactive
energy 3-phase
kvarh
90
91
186
187
282
283
R
47
Produced capacitive
reactive energy 3-phase
kvarh
Produced capacitive
reactive energy 3-phase
kvarh
92
93
188
189
284
285
R
48
Produced apparent energy
3-phase
kVAh
Produced apparent energy
3-phase
kVAh
94
95
190
191
286
287
R
Para-
meter
no.
NZM…-XMC-…
NZM-XMC-TC-MB
Actual
value
register
Maximum
value
register
Minimum
value
register
R/W
Parameters
Unit
Mode parameter
Unit
high
low
high
low
high
low