2 Installation
2.1 Basic devices
NZM-XMC Measuring and Communication Module
11/16 MN01219001Z-EN
www.eaton.com
9
▶
Fasten the device (if required) to the mounting plate.
For this the device does not have to be fastened separately, but is
simply secured by the cables or the distribution rail.
Figure 2: Attachment to the mounting plate
▶
Tighten the screws for the cable terminals.
Figure 3: Tightening the screws
DANGER
Danger of electrical shock!
For this wear protective gloves and use an insulated Allen key.
Screws must punch the copper in order to perform the voltage
sensing.
M5 x 80
DIN 912
NZM...-XMC
191 mm
(7.52”)
NZM...-4-XMC
233 mm
(9.17”)
M2.5
Top Cable Toxfree ZH RZ1-K:
1.8 - 2 Nm
(15.9 - 17.7 lb-in)