NFX9000 Adjustable Frequency Drives
B-2
For more information visit:
www.EatonElectrical.com
MN04002003E
February 2006
Table B-1: Communication Address Definition, continued
Content:
Address:
Function:
Status
monitor
Read-only
2100H
Error code:
0: No errors occurred
1: Over-current (oc)
2: Over-voltage (ov)
3: Overheat (oH)
4: Overload (oL)
5: Overload1 (oL1)
6: External fault (EF)
7: Reserved
8: Reserved
9: Current exceeds 2 times rated current during acc. (ocA)
10: Current exceeds 2 times rated current during dec. (ocd)
11: Current exceeds 2 times rated current during steady state operation
(ocn)
12: Reserved
13: Reserved
14: Low voltage (Lv)
15: CPU failure 1 (cF1)
16: CPU failure 2 (cF2)
17: b.b.
18: Overload (oL2)
19: Auto acc/dec failure ( cFA)
20: Software protection enabled (codE)
21: Reserved
22: CPU failure (cF3.1)
23: CPU failure (cF3.2)
24: CPU failure (cF3.3)
25: CPU failure (cF3.4)
26: CPU failure (cF3.5)
27: CPU failure (cF3.6)
28: CPU failure (cF3.7)
29: Hardware protection failure (HPF.1)
30: Hardware protection failure (HPF.2)
31: Hardware protection failure (HPF.3)
2101H
Status of AMD
Bit 1,0
00: RUN LED light off, STOP LED light up
01: RUN LED blink, STOP LED light up
10: RUN LED light up, STOP LED blink
11: RUN LED light up, STOP LED light off
Bit 2
1: JOG active
Bit 4,3
00: REV LED light off, FWD LED light up
01: REV LED blink, FWD LED light up
10: REV LED light up, FWD LED blink
11: REV LED light up, FWD LED light off