background image

9

INM 7700 Rev 12

5 .3 .5 

Bonding practice when hazardous-area equipment 

cannot meet prescribed insulation standards

Where hazardous-area equipment is connected to earth (either 
directly or indirectly) and/or it will not withstand a 500V insulation 
test to ground or the alternative described in section 5.3.4, 
eg, strain-gauge bridges with low-voltage insulation, pH and 
conductivity sensors, bare and/or earthed thermocouples, and 
some level detectors, the following considerations apply:

Safety considerations

a) The pipe, vessel, or body of the hazardous-area apparatus and/

or the adjacent metallic structure must be connected to the 
barrier DIN-rail (see item d) by a bonding conductor of at least 
4mm

2

 cross-sectional area for lengths of 100m or less; or at 

least 8mm

2

 area for lengths between 100m and 200m.

b) Where bonding conductors are used, care must be taken to 

avoid invading other intrinsically safe systems (those not using 
bonding conductors) by elevation arising from currents which 
may flow in the common earthing systems as a result of the 
presence of the bonding conductor. Where this possibility 
cannot be avoided, then barriers associated with bonded 
systems should be mounted on a separate DIN-rail from those 
on which other barriers are mounted. Additionally, the DIN-
rails themselves should also be earthed separately.

c) The hazardous-area equipment and/or adjacent metallic 

structure bond connections must be secured against vibration 
and corrosion. A terminal of the type used on ‘increased 
safety’ (‘e’) equipment is the mandatory solution.

d) 

The barrier DIN-rail connections must provide suitable 
termination facilities for the bonding conductor and usual 
‘earth return’ by being equipped with separate increased 
safety (‘e’) terminals.

Operational requirements

e) Figure 18 shows the 0V rail of the safe-area equipment returned 

to the barrier DIN-rail by a separate insulated conductor and 
the structural earths of any safe-area equipment returned 
separately to the neutral star-point. This reduces interference 
problems but is not essential for safety reasons.

f) In general, the use of barriers in all measurement leads 

reduces the possibility of earth circulating currents causing 
measurement problems.

g) Resistance from the neutral star point to ‘terrestrial earth’ – via 

the buried earth mat or rods – is determined by other 
regulations and is not modified or determined by the intrinsic 
safety requirements, which are concerned with the plant earth 
only.

5 .4 

Connections to dummy barriers

See figure 19. The MTL7799 dummy barriers provide safe 
connection facilities for unused cable cores, cable screens and 
0V returns. In addition, safe-area terminals 2 and 1 are connected 
internally to provide a straight ‘feedthrough’ 24V dc supply 
connection, enabling the units to be used as feed modules for 
use with a power bus, useful in applications where the fault trip 
mechanism of the MTL7798 is not needed.

6 MAINTENANCE

6 .1 General

Circuits in all MTL7700 range of barriers are encapsulated and so 
cannot be repaired. However, provided they are correctly installed 
and connected (as described in sections 4 and 5 of this manual) 
and the circuits they protect are not themselves defective, barrier 
faults are highly unlikely to occur. Therefore, servicing of barrier 
installations consists mainly of routine inspection and earth testing 
as described in this section.

More information about the maintenance of barrier installations is 
given in BS EN 60079 -17.

6 .2 

Routine inspection

At intervals not exceeding two years (more frequently for harsh 
environments), make a visual check of the barrier installation. 
Personnel undertaking these checks should comply with all 
regulations relating to the safety of plant and personnel. Care must 
be taken to prevent any inadvertent direct connection between 
hazardous- and safe-area circuits and, at all times, the safety 
precautions discussed in section 3 MUST be observed.

Figure 17: 

Earthing and screening using module earth terminals or earth rail alternative

Summary of Contents for MTL7700

Page 1: ...MTL7700 range Shunt diode safety barriers September 2017 INM 7700 Rev 12 Instruction manual MTL intrinsic safety solutions...

Page 2: ...evaluated by MHSA and judged to meet the applicable requirements of Title 30 Code of Federal Regulations Part 18 68 30 CFR Part 18 68 provided that a relevant installation complies with the following...

Page 3: ...tions 7 5 3 Connections to plant earth 7 5 4 Connections to dummy barriers 9 6 MAINTENANCE 9 6 1 General 9 6 2 Routine inspection 9 7 FAULT FINDING 10 7 1 Introduction 10 7 2 Power supply check 11 7 3...

Page 4: ...osure which offers an additional degree of protection appropriate to the area classification c Unless already protected by design this equipment must be protected by a suitable enclosure against i mec...

Page 5: ...e publications are available either from our website www mtl inst com or on request from your local office 2 DESCRIPTION 2 1 Introduction MTL7700 range of fourth generation intrinsically safe shunt di...

Page 6: ...rking barrier locations Supplied with labels in 1m lengths for cutting to size TGL7700 Spare labels for use with TAG57 tagging strips 0 5m strips supplied in sets of 10 IMB57 Tagging strip supports Tw...

Page 7: ...minimum of two c IMB57 tagging strip support 16 0mm minimum of two if specified d ISP7000 insulating spacer 14 7mm minimum of two if specified e ERB57S or O earth rail 8 mm minimum of two mounting bra...

Page 8: ...2 4 1 6 2 Make sure the barriers are of the correct type and polarity as specified in the safety documentation 3 4 1 Make sure all barriers are mounted the right way round and are properly attached so...

Page 9: ...her end of a column of barriers to provide redundancy and to simplify earth testing procedures WARNING Apart from rare occasions when the mounting surface carries the IS earth the ONLY method of provi...

Page 10: ...57 The tagging strip assembly figure 12 identifies the location of individual barriers ensuring that they are replaced correctly after removal for maintenance or testing Once installed the tagging str...

Page 11: ...for specific connections for individual barriers and applications 5 2 3 Bussed Power applications and connections When a number of barriers use a common power supply the optional power link BPL7700 ca...

Page 12: ...e section 4 3 4 an earth conductor normally copper wire with a cross sectional area of at least 4mm2 12AWG must be connected between ETM7 earth terminals located at each end of the rail and the spare...

Page 13: ...the structural earths of any safe area equipment returned separately to the neutral star point This reduces interference problems but is not essential for safety reasons f In general the use of barri...

Page 14: ...systems are relatively simple and their operation is easy to check However when fault finding is necessary it must only be undertaken after checking with plant personnel responsible for safety that i...

Page 15: ...s To overcome this problem the thermocouple circuits can be protected by using an MTL7760ac barrier as shown in figure 21 This permits the thermocouple output to be measured without needing special au...

Page 16: ...however the changeover switch and current selector reduce the need for connection changes d Using a high resistance in series with the barrier gives more stable results and makes it easier to set the...

Page 17: ...itch inputs with line fault detection To verify correct operation proceed as follows a Connect the barrier as shown in figure 30 b With an ohmeter check the status of the output contacts according to...

Page 18: ...050 Vfz x 1 10 11 4 10 5 11 6 7764 12 1k 12 1010 1050 Vfz x 1 10 11 4 10 5 11 6 7767 15 100 150 110 119 Vfz x 1 12 13 6 12 4 13 7 7779 28 300 93 311 333 Vfz x 2 25 9 26 3 26 26 5 7796 26 300 87 311 33...

Page 19: ...sistance Diode Test ve Diode Test ve Terminal Voltage 10 A Terminal Voltage 20mA V mA Min Max Min Max Min Max 7755ac 3 10 300 15 19 Vfd x 3 Vfd x 3 1 2 1 1 8 2 4 7756ac 3 10 300 15 19 Vfd x 2 Vfd x 2...

Page 20: ...end Resistance Diode Test ve Diode Test ve Terminal Voltage 10 A Terminal Voltage 20mA V mA Min Max Min Max Min Max 7787 28 300 93 311 333 Vfz x 2 26 6 27 4 26 7 27 6 7787 ch2 28 0 9V 26 Vfz x 2 26 6...

Page 21: ...hannel switch proximity input Hazardous Area Figure A8 Single channel switch proximity input Hazardous Area Figure A4 2 wire transmitter switch input Safe Area 3 4 1 2 MTL7789 7 8 5 6 Power 26 6V Powe...

Page 22: ...mV Sense Figure A13 Strain gauge bridges Hazardous Area Safe Area 3 4 1 2 MTL7745 5 6 620 10k 22 9 30V LFD COM CH 1 Power Bus Figure A10 Single channel switch proximity input with Line Fault Detect H...

Page 23: ...1 47 78 0 471 b 1 41 0 34 29 0 942 c 0 125 1 15 39 0 942 MTL7767 a1 a2 0 58 1 45 66 0 56 b 0 58 0 32 22 1 125 MTL7778 ac a1 a2 0 083 16 107 0 33 b 0 083 3 05 4 2 42 0 33 MTL7779 a1 a2 0 083 3 05 4 2 5...

Page 24: ...ndia No 36 Nehru Street Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San B...

Reviews: