Eaton MTL7700 Instruction Manual Download Page 15

11

INM 7700 Rev 12

7 .2 

Power supply check

Check that the power supply to an individual barrier circuit (or to 
an MTL7798 power feed module or an MTL7799 dummy barrier 
sourcing the power bus ) is functional and that the voltage across 
the supply with respect to earth is correct. For example, in Figure 20 
the presence of 24V on terminal 1 and 12V on terminal 2 when the 
switch in the hazardous area is closed confirms the serviceability 
of almost the complete circuit.

7 .3 

Barrier resistance test

To test the resistance of a barrier on site, refer to figure 20 and 
carry out the following procedure:

a) Unplug hazardous-area cables from terminals 3 and 4.

b) Unplug safe-area cables from terminals 1 and 2.

WARNING: Take care when handling safe-area cables; the 
relay contacts in figure 20 for example could be carrying 
mains voltage .

c) 

Measure the end-to-end resistance of the barrier by 
connecting a digital multimeter (set to a suitable Ω range) 
between terminals 1 and 3. The reading should typically be 
slightly less (eg 1–3% lower) than the maximum end-to-end 
resistance listed in tables 4 to 10 for the appropriate barrier 
type or approximately 10–20% higher than the figure specified 
in the safety description.

d) Check the functioning of the diode-return channel (, 

7787P+, only) by selecting the diode test function on the 
multimeter and connecting it between terminals 4 (+ve) and 2 
(–ve). This measures the forward voltage drop of the Schottky 
diodes in the chain: the reading should be less than 0.9V. 
Repeat the test with the connections reversed (ie, terminals 
4 (–ve) and 2 (+ve) for an expected reading of ∞ for the reverse 
voltage drop.

e) Tests c) and d) confirm the continuity of both barrier channels. 

If either channel is open-circuit it is most likely that the fuse 
has blown. The safe-area circuit should be investigated in an 
attempt to discover the cause of the fault. 

Note: 

if the barrier is removed, make sure the safe-area and 

hazardous-area cables disconnected during operations 

a)

 and 

b)

 are connected to an earth-rail, a dummy barrier or insulated 

completely.

c) If it is not possible to disconnect wiring to the barrier for steps 

a) and b), carry out the tests given in table 4.

EQUIPMENT AND BARRIER TESTS

8 .1 

Thermocouple and RTD tests

8 .1 .1 

Thermocouple circuit testing

Thermocouple test and calibration equipment is rarely certified 
intrinsically safe and therefore requires special authorisation before 
it can be used for testing or calibrating thermocouple circuits in 
hazardous areas. To overcome this problem, the thermocouple 
circuits can be protected by using an MTL7760ac barrier as 
shown in figure 21. This permits the thermocouple output to be 
measured without needing special authorisation to use uncertified 
thermocouple test equipment.

As it is seldom possible to measure accurately the temperatures of 
thermocouples located in hazardous areas, a safe way of adjusting 
calibration tables to compensate for plant temperatures is needed.  
This can be done by disconnecting the compensating cables from 
the thermocouple, shorting them together, and measuring the 
temperature of the shorting point.

8 .1 .2 

Resistance temperature detector (RTD) circuit 

testing

Resistance temperature detector (RTD) circuits can be tested 
by disconnecting the measuring leads from the RTD head in 
the hazardous area and connecting them to a resistance box. 
Sometimes it is more convenient to connect the resistance box in 
the safe area, for instance at point ‘xx’ in figure 22. For the latter 
method, however, the RTD must be shorted out or an allowance 
made for its temperature. The effect of a negative temperature 
change can be simulated by connecting the resistance box into the 
measurement lead at point ‘yy’. The advantage of connecting the 
resistance box at the RTD head is that any leakage can also be 
determined by connecting the resistance box at point ‘yy’.

8 .2 

Barrier tests

8 .2 .1 General

MTL7700 range of barriers do not need to be subjected to routine 
testing if they are in normal use. Generally, the inspection tests 
described in section 6 are more than adequate. However, if the 
performance of barriers is in any way suspect, then carry out the 
detailed tests described in this section. Barriers which pass these 
tests satisfactorily are highly unlikely to represent an unacceptable 
level of risk or cause a circuit malfunction.

There are two types of test (as shown by tables 4 to 10); a simple 
test using a digital multimeter to test barriers on site and a more 
comprehensive bench test using a constant current source to 
establish the breakdown characteristics.

Although certification requirements concentrate on pulse-
current tests, in many ways the leakage current tests described 
in this section are a more satisfactory method of testing suspect 
diodes. If a complete functional check of a barrier is needed, then 
the multimeter and constant current tests described in sections 
8.2.2 and 8.2.3 should be made although, for most purposes, the 
multimeter tests should suffice.


 



Figure 20:

  Switch-status transfer circuit using an MTL7787 barrier

1

2

3
4

1

2

3
4

Compensating cables

Safe-area

equipment

Calibration

equipment

MTL7760ac

Figure 21: 

 Calibrating a thermocouple barrier circuit

Summary of Contents for MTL7700

Page 1: ...MTL7700 range Shunt diode safety barriers September 2017 INM 7700 Rev 12 Instruction manual MTL intrinsic safety solutions...

Page 2: ...evaluated by MHSA and judged to meet the applicable requirements of Title 30 Code of Federal Regulations Part 18 68 30 CFR Part 18 68 provided that a relevant installation complies with the following...

Page 3: ...tions 7 5 3 Connections to plant earth 7 5 4 Connections to dummy barriers 9 6 MAINTENANCE 9 6 1 General 9 6 2 Routine inspection 9 7 FAULT FINDING 10 7 1 Introduction 10 7 2 Power supply check 11 7 3...

Page 4: ...osure which offers an additional degree of protection appropriate to the area classification c Unless already protected by design this equipment must be protected by a suitable enclosure against i mec...

Page 5: ...e publications are available either from our website www mtl inst com or on request from your local office 2 DESCRIPTION 2 1 Introduction MTL7700 range of fourth generation intrinsically safe shunt di...

Page 6: ...rking barrier locations Supplied with labels in 1m lengths for cutting to size TGL7700 Spare labels for use with TAG57 tagging strips 0 5m strips supplied in sets of 10 IMB57 Tagging strip supports Tw...

Page 7: ...minimum of two c IMB57 tagging strip support 16 0mm minimum of two if specified d ISP7000 insulating spacer 14 7mm minimum of two if specified e ERB57S or O earth rail 8 mm minimum of two mounting bra...

Page 8: ...2 4 1 6 2 Make sure the barriers are of the correct type and polarity as specified in the safety documentation 3 4 1 Make sure all barriers are mounted the right way round and are properly attached so...

Page 9: ...her end of a column of barriers to provide redundancy and to simplify earth testing procedures WARNING Apart from rare occasions when the mounting surface carries the IS earth the ONLY method of provi...

Page 10: ...57 The tagging strip assembly figure 12 identifies the location of individual barriers ensuring that they are replaced correctly after removal for maintenance or testing Once installed the tagging str...

Page 11: ...for specific connections for individual barriers and applications 5 2 3 Bussed Power applications and connections When a number of barriers use a common power supply the optional power link BPL7700 ca...

Page 12: ...e section 4 3 4 an earth conductor normally copper wire with a cross sectional area of at least 4mm2 12AWG must be connected between ETM7 earth terminals located at each end of the rail and the spare...

Page 13: ...the structural earths of any safe area equipment returned separately to the neutral star point This reduces interference problems but is not essential for safety reasons f In general the use of barri...

Page 14: ...systems are relatively simple and their operation is easy to check However when fault finding is necessary it must only be undertaken after checking with plant personnel responsible for safety that i...

Page 15: ...s To overcome this problem the thermocouple circuits can be protected by using an MTL7760ac barrier as shown in figure 21 This permits the thermocouple output to be measured without needing special au...

Page 16: ...however the changeover switch and current selector reduce the need for connection changes d Using a high resistance in series with the barrier gives more stable results and makes it easier to set the...

Page 17: ...itch inputs with line fault detection To verify correct operation proceed as follows a Connect the barrier as shown in figure 30 b With an ohmeter check the status of the output contacts according to...

Page 18: ...050 Vfz x 1 10 11 4 10 5 11 6 7764 12 1k 12 1010 1050 Vfz x 1 10 11 4 10 5 11 6 7767 15 100 150 110 119 Vfz x 1 12 13 6 12 4 13 7 7779 28 300 93 311 333 Vfz x 2 25 9 26 3 26 26 5 7796 26 300 87 311 33...

Page 19: ...sistance Diode Test ve Diode Test ve Terminal Voltage 10 A Terminal Voltage 20mA V mA Min Max Min Max Min Max 7755ac 3 10 300 15 19 Vfd x 3 Vfd x 3 1 2 1 1 8 2 4 7756ac 3 10 300 15 19 Vfd x 2 Vfd x 2...

Page 20: ...end Resistance Diode Test ve Diode Test ve Terminal Voltage 10 A Terminal Voltage 20mA V mA Min Max Min Max Min Max 7787 28 300 93 311 333 Vfz x 2 26 6 27 4 26 7 27 6 7787 ch2 28 0 9V 26 Vfz x 2 26 6...

Page 21: ...hannel switch proximity input Hazardous Area Figure A8 Single channel switch proximity input Hazardous Area Figure A4 2 wire transmitter switch input Safe Area 3 4 1 2 MTL7789 7 8 5 6 Power 26 6V Powe...

Page 22: ...mV Sense Figure A13 Strain gauge bridges Hazardous Area Safe Area 3 4 1 2 MTL7745 5 6 620 10k 22 9 30V LFD COM CH 1 Power Bus Figure A10 Single channel switch proximity input with Line Fault Detect H...

Page 23: ...1 47 78 0 471 b 1 41 0 34 29 0 942 c 0 125 1 15 39 0 942 MTL7767 a1 a2 0 58 1 45 66 0 56 b 0 58 0 32 22 1 125 MTL7778 ac a1 a2 0 083 16 107 0 33 b 0 083 3 05 4 2 42 0 33 MTL7779 a1 a2 0 083 3 05 4 2 5...

Page 24: ...ndia No 36 Nehru Street Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San B...

Reviews: