background image

9

INM7700-6   

Jan 2010

5.3.5

Bonding practice when hazardous-area 
equipment cannot meet prescribed insulation 
standards

Where hazardous-area equipment is connected to earth (either
directly or indirectly) and/or it will not withstand a 500V insulation
test to ground or the alternative described in section 5.3.4, eg, strain-
gauge bridges with low-voltage insulation, pH and conductivity
sensors, bare and/or earthed thermocouples, and some level
detectors, the following considerations apply:

Safety considerations

a) The pipe, vessel, or body of the hazardous-area apparatus

and/or the adjacent metallic structure must be connected to the
barrier DIN-rail (see item d) by a bonding conductor of at least
4mm

2

cross-sectional area for lengths of 100m or less; or at least

8mm

2

area for lengths between 100m and 200m.

b) Where bonding conductors are used, care must be taken to

avoid invading other intrinsically safe systems (those not using
bonding conductors) by elevation arising from currents which
may flow in the common earthing systems as a result of the
presence of the bonding conductor. Where this possibility
cannot be avoided, then barriers associated with bonded
systems should be mounted on a separate DIN-rail from those on
which other barriers are mounted. Additionally, the DIN-rails
themselves should also be earthed separately.

c) The hazardous-area equipment and/or adjacent metallic

structure bond connections must be secured against vibration
and corrosion. A terminal of the type used on ‘increased safety’
(‘e’) equipment is the mandatory solution.

d) The barrier DIN-rail connections must provide suitable

termination facilities for the bonding conductor and usual ‘earth
return’ by being equipped with separate increased safety (‘e’)
terminals.

Operational requirements

e) Figure 18 shows the 0V rail of the safe-area equipment returned

to the barrier DIN-rail by a separate insulated conductor and the
structural earths of any safe-area equipment returned separately
to the neutral star-point. This reduces interference problems but
is not essential for safety reasons.

f) In general, the use of barriers in all measurement leads reduces

the possibility of earth circulating currents causing measurement
problems.

g) Resistance from the neutral star point to ‘terrestrial earth’ – via

the buried earth mat or rods – is determined by other regulations
and is not modified or determined by the intrinsic safety
requirements, which are concerned with the plant earth only.

5.4

Connections to dummy barriers

See figure 19. The MTL7799 dummy barriers provide safe
connection facilities for unused cable cores, cable screens and 0V
returns. In addition, safe-area terminals 2 and 1 are connected
internally to provide a straight ‘feedthrough’ 24V dc supply
connection, enabling the units to be used as feed modules for use
with a power bus, useful in applications where the fault trip
mechanism of the MTL7798 is not needed.

6

MAINTENANCE

6.1

General

Circuits in all MTL7700 Series barriers are encapsulated and so
cannot be repaired. However, provided they are correctly installed
and connected (as described in sections 4 and 5 of this manual) and
the circuits they protect are not themselves defective, barrier faults are
highly unlikely to occur. Therefore, servicing of barrier installations
consists mainly of routine inspection and earth testing as described in
this section.

More information about the maintenance of barrier installations is
given in BS EN 60079 -17.

6.2

Routine inspection

At intervals not exceeding two years (more frequently for harsh
environments), make a visual check of the barrier installation.
Personnel undertaking these checks should comply with all
regulations relating to the safety of plant and personnel. Care must
be taken to prevent any inadvertent direct connection between
hazardous- and safe-area circuits and, at all times, the safety
precautions discussed in section 3 

MUST

be observed.

TAG57

TGL7700

ERB57O

IMB57

ETL7000

ISP7000

ERL

(optional earth rail)

Cable screens

using earth rail

Cable screens

using module

terminals

ETM7

Figure 17: 

Earthing and screening using module earth terminals or earth rail alternative

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Summary of Contents for MTL770 Series

Page 1: ...Instruction Manual INM7700 MTL7700 Series Shunt diode safety barriers www calcert com sales calcert com 1 888 610 7664 0 5 10 15 20 25 30...

Page 2: ...ii INM7700 6 Jan 2010 www calcert com sales calcert com 1 888 610 7664 0 5 10 15 20 25 30...

Page 3: ...h 7 5 4 Connections to dummy barriers 9 6 MAINTENANCE 9 6 1 General 9 6 2 Routine inspection 9 7 FAULT FINDING 10 7 1 Introduction 10 7 2 Power supply check 11 7 3 Barrier resistance test 11 8 EQUIPME...

Page 4: ...INM7700 6 Jan 2010 iv www calcert com sales calcert com 1 888 610 7664 0 5 10 15 20 25 30...

Page 5: ...are available either from the company website www mtl inst com or on request from your local MTL office 2 DESCRIPTION 2 1 Introduction MTL7700 Series fourth generation intrinsically safe shunt diode s...

Page 6: ...ers for marking barrier locations Supplied with labels in 1m lengths for cutting to size TGL7700 Spare labels for use with TAG57 tagging strips 0 5m strips supplied in sets of 10 IMB57 Tagging strip s...

Page 7: ...en length of DIN rail allow space length for a Barrier packing pitch 12 6mm b ETL7000 earth terminals 10mm each minimum of two c IMB57 tagging strip support 16 0mm minimum of if specified two d ISP700...

Page 8: ...recommendations contained in the relevant sections of IEC 60079 14 for the gas group temperature classification and area classification required 2 4 1 6 2 Make sure the barriers are of the correct typ...

Page 9: ...end of a column of barriers to provide redundancy and to simplify earth testing procedures WARNING Apart from rare occasions when the mounting surface carries the IS earth the ONLY method of providin...

Page 10: ...bly figure 12 identifies the location of individual barriers ensuring that they are replaced correctly after removal for maintenance or testing Once installed the tagging strip pivots upwards to provi...

Page 11: ...vidual barriers and applications 5 2 3 Bussed Power applications and connections When a number of barriers use a common power supply the optional power link BPL7700 can be used Typical applications in...

Page 12: ...or normally copper wire with a cross sectional area of at least 4mm2 12AWG must be connected between ETM7 earth terminals located at each end of the rail and the spare terminals on the ETL7000 termina...

Page 13: ...educes interference problems but is not essential for safety reasons f In general the use of barriers in all measurement leads reduces the possibility of earth circulating currents causing measurement...

Page 14: ...ck However when fault finding is necessary it must only be undertaken after checking with plant personnel responsible for safety that it is safe to proceed The fault finding procedures described in th...

Page 15: ...by using an MTL7760ac barrier as shown in figure 21 This permits the thermocouple output to be measured without needing special authorisation to use uncertified thermocouple test equipment As it is se...

Page 16: ...rehensive testing requires specialised equipment beyond the scope of on site tests However an effective test which will confirm that the unit is operating correctly is shown in figure 24 Ammeter 1 mea...

Page 17: ...he output contacts according to Table 3 3 4 1 2 MTL7742 5 6 7 8 Bussed Power 24V Vs Vs 2K Figure 27 Test circuit for MTL7742 3 4 1 2 MTL7745 5 6 620W 10kW 24V Bussed Power Line Fault Output Vs Vs Figu...

Page 18: ...e the expected reading across the diode chain can be determined BARRIER DATA MULTIMETER TESTS CONSTANT CURRENT TESTS MTL Safety End to end Diode Diode Terminal Terminal model Description Resistance Te...

Page 19: ...7 Dual channel ac barriers BARRIER DATA MULTIMETER TESTS CONSTANT CURRENT TESTS MTL Safety End to end Diode Diode Terminal Terminal model Description Resistance Test Test Voltage Voltage No ve ve 10 A...

Page 20: ...fz x 2 26 6 27 4 26 7 27 6 7787 ch2 28 0 9V 26 Vfz x 2 26 6 27 4 26 7 27 6 7787P 28 237 119 241 253 Vfz x 3 26 4 27 4 26 5 27 6 7787P ch2 28 0 9V 26 Vfz x 2 26 6 27 4 26 7 27 6 7789 38 300 93 614 651...

Page 21: ...ceiver Figure A6 Low level analogue inputs RTD s Figure A2 2 wire transmitters with 250 conditioning Hazardous Area Safe Area 3 4 1 2 MTL7760ac MTL7765ac MTL7778ac Recorder Controller Data logger Comp...

Page 22: ...3 4 1 2 MTL7745 5 6 620 10k 22 9 30V LFD COM CH 1 Power Bus Figure A10 Single channel switch proximity input with Line Fault Detect Hazardous Area Safe Area 3 4 1 2 MTL7789 7 8 5 6 Power 26V Power 26V...

Page 23: ...www calcert com sales calcert com 1 888 610 7664 0 5 10 15 20 25 30...

Page 24: ...91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail sales mtlindia com MTL Italia srl Via Cant 11 I 20092 Cinisello Balsamo MI Italy Tel 39 0 2 61802011 Fax 39 0 2 61294560 E mail info mtl inst it M...

Reviews: