background image

12

INM7700-6   

Jan 2010

8.2.2

Multimeter tests

See tables 4 to 10. The use of a digital multimeter for testing barriers
is described in section 7. The tables assume that the multimeter is set
to a suitable 

Ω

range for the end-to-end resistance tests (except for

diode return channels) and for the continuity tests; and that the
multimeter diode test function is used for the diode tests, channel
isolation tests and for the end-to-end resistance tests for diode return
channels.

8.2.3

Constant-current tests

For these tests (last column of tables 4 to 10) a constant-current
generator capable of supplying 10µA, 20mA and 40mA currents
from a 30V source is needed. Ideally, a purpose-built current
generator should be used but, alternatively, a set-up based on a
laboratory power supply and two multimeters (figure 23) will serve.
The current is measured by one multimeter and trimmed by adjusting
the output voltage of the power supply indicated on the second
multimeter.

When using a constant-current generator for testing MTL7700 Series
barriers, note the following points:

a) The current must be limited to 50mA to avoid damaging the

barriers.

b) The accuracy of the current is not critical and can vary by ±5%.
c) Test leads must be connected securely to the barrier terminals;

however, the changeover switch and current selector reduce the
need for connection changes.

d) Using a high resistance in series with the barrier gives more

stable results and makes it easier to set the required current.

8.3

Tests for Active Barriers

8.3.1

Tests for the

Comprehensive testing requires specialised equipment, beyond the
scope of on-site tests. However, an effective test which will confirm
that the unit is operating correctly is shown in figure 24. Ammeter 1
measures the transmitter simulator current of between 4 and 20mA
flowing from terminal 4 and the safe-area load current flowing to
terminal 4 simultaneously. Since these two currents are equal and
opposite, the resulting reading on the ammeter should be virtually
zero. Ammeter 2 verifies the presence of the 4–20mA transmitter
signal.

1

2

3

4

5

7

Bridge supply

Measurement

Safe-area

equipment

MTL7756ac

Variable

resistance

Measurement

Variable

resistance

y

y

x

x

Figure 22:

Calibrating an RTD barrier circuit

To barrier on test

Digital

multimter

(current)

Digital

multimter

(voltage)

current

selector

current limited

to 30mA

2-channel laboratory power supply

0 - 30V

variable

0 - 30V

variable

+   -

+    -

Changeover

switch

40mA

20mA

10

m

A

3M

W

1.5k

W

750

W

Figure 23:

Constant-current test circuit using a power supply

and digital multimeters

1

2

3
4

A1

A2

Transmitter

simulator

4-20mA

250

W

+20 to

35Vdc

+

+

_

_

Figure 24:

test circuit

8.3.2

Tests for the

Since this unit incorporates a built-in protection circuit, it has to be
tested in a different manner to an ordinary shunt-diode barrier.
Referring to figure 25, set the transmitter simulator to 4mA and to
20mA, and check that the ammeter reads approximately the same
value. Then, having set the simulator to 20mA, check that the voltage
between terminals 1 and 3 is less than 8.5V and between terminals
2 and 4 is less than 1.6V.

Figure 25:

test circuit

1

2

3
4

A

Transmitter

simulator

4-20mA

+20 to

35Vdc

250

W

+

_

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Summary of Contents for MTL770 Series

Page 1: ...Instruction Manual INM7700 MTL7700 Series Shunt diode safety barriers www calcert com sales calcert com 1 888 610 7664 0 5 10 15 20 25 30...

Page 2: ...ii INM7700 6 Jan 2010 www calcert com sales calcert com 1 888 610 7664 0 5 10 15 20 25 30...

Page 3: ...h 7 5 4 Connections to dummy barriers 9 6 MAINTENANCE 9 6 1 General 9 6 2 Routine inspection 9 7 FAULT FINDING 10 7 1 Introduction 10 7 2 Power supply check 11 7 3 Barrier resistance test 11 8 EQUIPME...

Page 4: ...INM7700 6 Jan 2010 iv www calcert com sales calcert com 1 888 610 7664 0 5 10 15 20 25 30...

Page 5: ...are available either from the company website www mtl inst com or on request from your local MTL office 2 DESCRIPTION 2 1 Introduction MTL7700 Series fourth generation intrinsically safe shunt diode s...

Page 6: ...ers for marking barrier locations Supplied with labels in 1m lengths for cutting to size TGL7700 Spare labels for use with TAG57 tagging strips 0 5m strips supplied in sets of 10 IMB57 Tagging strip s...

Page 7: ...en length of DIN rail allow space length for a Barrier packing pitch 12 6mm b ETL7000 earth terminals 10mm each minimum of two c IMB57 tagging strip support 16 0mm minimum of if specified two d ISP700...

Page 8: ...recommendations contained in the relevant sections of IEC 60079 14 for the gas group temperature classification and area classification required 2 4 1 6 2 Make sure the barriers are of the correct typ...

Page 9: ...end of a column of barriers to provide redundancy and to simplify earth testing procedures WARNING Apart from rare occasions when the mounting surface carries the IS earth the ONLY method of providin...

Page 10: ...bly figure 12 identifies the location of individual barriers ensuring that they are replaced correctly after removal for maintenance or testing Once installed the tagging strip pivots upwards to provi...

Page 11: ...vidual barriers and applications 5 2 3 Bussed Power applications and connections When a number of barriers use a common power supply the optional power link BPL7700 can be used Typical applications in...

Page 12: ...or normally copper wire with a cross sectional area of at least 4mm2 12AWG must be connected between ETM7 earth terminals located at each end of the rail and the spare terminals on the ETL7000 termina...

Page 13: ...educes interference problems but is not essential for safety reasons f In general the use of barriers in all measurement leads reduces the possibility of earth circulating currents causing measurement...

Page 14: ...ck However when fault finding is necessary it must only be undertaken after checking with plant personnel responsible for safety that it is safe to proceed The fault finding procedures described in th...

Page 15: ...by using an MTL7760ac barrier as shown in figure 21 This permits the thermocouple output to be measured without needing special authorisation to use uncertified thermocouple test equipment As it is se...

Page 16: ...rehensive testing requires specialised equipment beyond the scope of on site tests However an effective test which will confirm that the unit is operating correctly is shown in figure 24 Ammeter 1 mea...

Page 17: ...he output contacts according to Table 3 3 4 1 2 MTL7742 5 6 7 8 Bussed Power 24V Vs Vs 2K Figure 27 Test circuit for MTL7742 3 4 1 2 MTL7745 5 6 620W 10kW 24V Bussed Power Line Fault Output Vs Vs Figu...

Page 18: ...e the expected reading across the diode chain can be determined BARRIER DATA MULTIMETER TESTS CONSTANT CURRENT TESTS MTL Safety End to end Diode Diode Terminal Terminal model Description Resistance Te...

Page 19: ...7 Dual channel ac barriers BARRIER DATA MULTIMETER TESTS CONSTANT CURRENT TESTS MTL Safety End to end Diode Diode Terminal Terminal model Description Resistance Test Test Voltage Voltage No ve ve 10 A...

Page 20: ...fz x 2 26 6 27 4 26 7 27 6 7787 ch2 28 0 9V 26 Vfz x 2 26 6 27 4 26 7 27 6 7787P 28 237 119 241 253 Vfz x 3 26 4 27 4 26 5 27 6 7787P ch2 28 0 9V 26 Vfz x 2 26 6 27 4 26 7 27 6 7789 38 300 93 614 651...

Page 21: ...ceiver Figure A6 Low level analogue inputs RTD s Figure A2 2 wire transmitters with 250 conditioning Hazardous Area Safe Area 3 4 1 2 MTL7760ac MTL7765ac MTL7778ac Recorder Controller Data logger Comp...

Page 22: ...3 4 1 2 MTL7745 5 6 620 10k 22 9 30V LFD COM CH 1 Power Bus Figure A10 Single channel switch proximity input with Line Fault Detect Hazardous Area Safe Area 3 4 1 2 MTL7789 7 8 5 6 Power 26V Power 26V...

Page 23: ...www calcert com sales calcert com 1 888 610 7664 0 5 10 15 20 25 30...

Page 24: ...91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail sales mtlindia com MTL Italia srl Via Cant 11 I 20092 Cinisello Balsamo MI Italy Tel 39 0 2 61802011 Fax 39 0 2 61294560 E mail info mtl inst it M...

Reviews: