Modbus MS Card
– User Manual
34009048XT_EN/AD
Page
39/55
6.7 Data for Eaton 9E
6.7.1 Status table
Status description
Status to 0
Status to 1
Word (hex)
Bit
Load protected
no
yes
40
0
UPS coupled
no
yes
40
1
Unit general alarm
no
yes
40
2
UPS in backup
no
yes
40
4
Battery low warning
no
yes
40
5
Low battery
no
yes
40
6
Operation on static switch
no
yes
40
7
Communication fault
absent
present
40
9
UPS overload
no
yes
40
A
Emergency stop
absent
present
40
B
Battery to be checked
no
yes
40
D
Device ventilation fault
no
yes
40
E
Classe d’UPS
001 : off line / line interactive
011 : on line - unitary/parallel
100 : on line
– parallel with
NS
101 : on line
– hot standby
redundancy
41
1 to 3
Manual bypass switch (Q3BP)
open
closed
41
6
Mode ECO = 1
no
yes
41
7
Battery present
absent
present
42
0
Wiring fault
absent
present
44
2
Mains 1 voltage out of tolerance
no
yes
44
8
Mains 1 frequency out of tolerance
no
yes
44
B
Maintenance position
no
yes
46
1
Output on bypass
no
yes
46
7
Mains 2 voltage out of tolerance
no
yes
46
A
Mains 2 internal fault
absent
present
47
2
Charger general fault
no
yes
49
0
Battery charge
no
yes
49
1 & 3
Inverter major fault
no
yes
4C
1
Inverter overload
no
yes
4C
2
Short circuit
no
yes
4F
1