Modbus MS Card
– User Manual
34009048XT_EN/AD
Page
6/55
2.3 Technical characteristics
Functions
Parameters
Default values
Possible values
JBUS/MODBUS
communication
- Baud rate
- Parity
- Bit number
- Stop bit
- Slave number
- 9600 bauds
- without parity
- 8
- 2
- Slave nr 1
- 1200, 2400, 4800, 9600, 19200, 38400
- Without parity, even parity, odd parity
-
- 1, 2
- 1 to FF (hexadecimal)
RS232 link
- Link connection in
transmit data (Tx) or
receive data (Rx)
- Rx on pin 1
- Tx on pin 3
- Rx on pin 1
- Tx on pin 3
RS485 link
- Termination
- No termination
- With or without (2 or 4 wires)