Modbus MS Card
– User Manual
34009048XT_EN/AD
Page
30/55
6.4.2 Modular fault table
Description du Status
Status to 0
Status to 1
Word
(hex)
Bit
Module 1
General alarm
Absent
Present
61
0
Fan failure
Absent
Present
61
1
Internal communication fault
Absent
Present
61
2
Inverter thermal overload
Absent
Present
61
3
Inverter fault
Absent
Present
61
4
Inverter fuse blown
Absent
Present
61
5
Load short circuit
Absent
Present
61
6
Module 2
General alarm
Absent
Present
62
0
Fan failure
Absent
Present
62
1
Internal communication fault
Absent
Present
62
2
Inverter thermal overload
Absent
Present
62
3
Inverter fault
Absent
Present
62
4
Inverter fuse blown
Absent
Present
62
5
Load short circuit
Absent
Present
62
6
Module 3
General alarm
Absent
Present
63
0
Fan failure
Absent
Present
63
1
Internal communication fault
Absent
Present
63
2
Inverter thermal overload
Absent
Present
63
3
Inverter fault
Absent
Present
63
4
Inverter fuse blown
Absent
Present
63
5
Load short circuit
Absent
Present
63
6
Module 4
General alarm
Absent
Present
64
0
Fan failure
Absent
Present
64
1
Internal communication fault
Absent
Present
64
2
Inverter thermal overload
Absent
Present
64
3
Inverter fault
Absent
Present
64
4
Inverter fuse blown
Absent
Present
64
5
Load short circuit
Absent
Present
64
6