Modbus MS Card
– User Manual
34009048XT_EN/AD
Page
25/55
6.2 Data for Pulsar M 2200 / 3000
6.2.1 Status table
Status description
Status to 0
Status to 1
Word (hex)
Bit
Load protected
no
yes
40
0
UPS coupled
no
yes
40
1
Unit general alarm
no
yes
40
2
UPS in backup
no
yes
40
4
Battery low warning
no
yes
40
5
Low battery
no
yes
40
6
Operation on static switch
no
yes
40
7
Communication fault
absent
present
40
9
UPS overload
no
yes
40
A
Emergency stop
absent
present
40
B
Battery to be checked
no
yes
40
D
Device ventilation fault
no
yes
40
E
Manual bypass switch (Q3BP)
open
closed
41
6
Battery present
absent
present
42
0
Mains 1 voltage out of tolerance
no
yes
44
8
Mains 1 frequency out of tolerance
no
yes
44
B
Redundancy lost
no
yes
45
7
Maintenance position
no
yes
46
1
Mains 2 overload
no
yes
46
5
Output on bypass
no
yes
46
7
Mains 2 frequency out of tolerance
no
yes
46
9
Mains 2 voltage out of tolerance
no
yes
46
A
Phase M2 out of tolerance
no
yes
46
B
Charger general fault
no
yes
49
0
Battery charge
no
yes
49
1 & 3
Converter fault
no
yes
4A
1
Inverter major fault
no
yes
4C
1