OPERATING INSTRUCTIONS

   MN280067EN   July 2017

Type MET electronic recloser control tester operating instructions

Tester

Test Selector switch (S6) in BATT. VOLTS—40V; Power switch 

(S1) OFF; power cord plugged into outlet (see CAUTION at 

beginning of OPERATING PROCEDURES section).

Battery voltage

1.  Plug the battery test cable, furnished with the tester, 

into the BATT. TEST terminals on the tester and the 

battery terminals on the control.

otee:

N

The spacing between the battery test-terminal 

posts on the tester is intentionally staggered to 

assure proper connection of the test cable plug. 

Make sure all three pins on the plug are properly 

seated in the three terminal posts.

The bar extension on the side of the plug at the other 

end of the battery test cable assures proper connection 

of the cable to the three-battery test-terminal posts 

on the electronic control. If the control is equipped 

with only two terminal posts, plug in the test cable 

with the two pins farthest from the bar extension 

engaged (Figure 3).

2.  Read the open circuit voltage of the battery on the 

dc meter. A fully charged Form 2, Form 3 or Form 3A 

battery will normally read 26—28 volts.

3.  Depress Battery Load Test switch (S7) for about two 

seconds (or just long enough to read the meter). For a 

fully charged Form 2, Form 3 or Form 3A battery, the 

voltage should not drop more than 3 volts from the 

open circuit voltage. (Typical drop will be 1.5 to 2 volts).

BAR

EXTENSION

ON PLUG

BATTERY

TEST

TERMINAL POSTS

ON CONTROL PANEL

BATTERY

LOCKOUT

INDICATOR

CONNECT THESE TWO

PINS TO THE TERMINAL POSTS

BATTERY TEST

CABLE PLUG

Figure 2 .  Battery-test cable connections to control with 

only two battery-test terminal posts

Battery discharge and charge rates

The MET tester can be used to measure battery discharge and 

charge rates on Form 2, Form 3 and Form 3A controls only.

1.  Connect the control to the tester with the proper test 

cable and energize the tester ON-OFF switch S1 to 

ON. Disconnect the jumper between the current (

|

terminals on controls equipped with three test terminals.

2.  Move the manual control switch on the electronic 

control panel to CLOSE and release. The target above 

the switch will show red.

3.  Turn Test Selector Switch S6 to DISCHARGE—(4 MA) 

and measure the battery drain. Normal quiescent battery 

drain measures 1.5 to 2.0 mA. Certain accessories can 

increase this nominal value above 4 mA. (See Table 2 

in Appendix A).

otee:

N

The 15-mA charging rate specified in Steps 4A, 

4B, and 4C is a nominal value based on a 27-volt 

battery and rated input parameters (e.g. 120 or 

240 Vac with potential chargers or 40- amp line 

current with recloser CT charger). Even under 

these standard conditions, a variation of ±2 mA 

may be observed in the charging rate.

4. 

A.  If the electronic control is equipped with a 115-Vac 

battery charger, turn Test Selector Switch S6 to 

CHARGE— (40 MA) and energize the charger circuit. 

The charging rate should be approximately 15 mA 

minus the discharge rate measured in Step 3.

B.  If power for the battery charger is supplied by a 

bushingcurrent transformer on the recloser (Type 

RE and WE reclosers) the following procedure may 

be used to check the charging rate.

otee:

N

A minimum of 40 amps line current through 

Phase B of the recloser is required to power 

the battery charger. This may be obtained 

from normal line-current flow through an 

on-line recloser, or in the case of a recloser 

removed from service, by manually closing 

the recloser and applying a low-voltage, 

highcurrent ac power supply across Phase B.

(1)  Using the interconnecting cables supplied with 

the tester, connect both the control and recloser 

to the appropriate receptacles on the tester.

otee:

N

The elbow plug of both test cables is 

connected to the tester.

(2)  With the recloser closed and a minimum of 

40 amps flowing through Phase B, turn Test 

Selector Switch S6 to CHARGE—(40 MA). The 

meter should read approximately 15 mA minus 

the discharge rate measured in Step 3.

C.  If power for the battery charger is supplied from 

a 230- Vac source in the operator cabinet of the 

motor driven reclosers, proceed as follows:
(1)  Using the interconnecting cables supplied with the 

tester, connect both the control and the recloser to 

the appropriate receptacles on the tester.

Summary of Contents for MET

Page 1: ...Type MET electronic recloser control tester operating instructions COOPER POWER SERIES Reclosers MN280067EN Effective July 2017 Supersedes February 2001 S280 76 1...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...F LIABILITY I SAFETY FOR LIFE III SAFETY INFORMATION III Safety instructions iii SHIPMENT AND ACCEPTANCE 1 DESCRIPTION 1 SPECIFICATIONS 1 DESCRIPTION AND USE OF OPERATING CONTROLS 2 OPERATING PROCEDUR...

Page 4: ...age lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally...

Page 5: ...ecloser simulator provides a 2 1 2 cycles time delay to duplicate the interrupting time of a Type RE recloser in response to a trip signal from the control when recloser clearing time tests are being...

Page 6: ...ight Indicates an open recloser during control testing 11 Recloser simulator closed light Indicates a closed recloser during control testing 12 Timer Measures time of test 13 S 10 Timer reset button R...

Page 7: ...tional operation of the recloser T216 2 To remove the control from service 1 Place the Ground Trip switch to BLOCK 2 Disconnect the recloser interconnecting cable at the receptacle on the bottom of th...

Page 8: ...equipped with three test terminals 2 Move the manual control switch on the electronic control panel to CLOSE and release The target above the switch will show red 3 Turn Test Selector Switch S6 to DIS...

Page 9: ...RECLOSING position 3 Ground Trip switch in NORMAL position 4 Control settings programmed for desired operating conditions Tester 1 All switches and controls in their OFF or extreme counterclockwise po...

Page 10: ...CONDITIONS 2 Form 3 family controls only to prevent overshooting while raising the test current to the minimum trip level remove the timing plug from socket 1 to provide instantaneous trip 3 Check to...

Page 11: ...om the electronic control Figures 4 and 5 in Appendix A show the control response and Types RE and RVE clearing TCC curves for some common Form 3A control phase trip and ground trip timing plugs To ch...

Page 12: ...irst trip check that the control and tester settings are as specified under INITIAL CONDITIONS and proceed as follows 1 Remove the first Reclosing Interval Delay plug from the control panel and progra...

Page 13: ...h the control battery providing closing coil or closing motor energy is available at the recloser Initial conditions Control Battery connected and control in lockout verify with Lockout Test switch an...

Page 14: ...ypical phase trip TCC curves for Types RE and RVE reclosers 11 Figure 5 Typical ground trip TCC curves for Types RE and RVE reclosers 11 Table 2 Quiescent Drain of Form 2 and Form 3 Family Control Acc...

Page 15: ...KA522ME Remote minimum trip doubler 0 Supervisory contacts open 5 7 Supervisory contacts closed KA531ME Fuse elimination 0 KA533ME Dc supply adapter See KA339ME KA542ME Heater 0 KA545ME Load current i...

Page 16: ...eclose 0 KA2035ME2 Remote non reclose and remote ground trip block maintained 22 Supervisory contacts open 85 Supervisory contacts closed KA2039ME2 Recloser status 06 Recloser Open 16 Recloser Closed...

Page 17: ...three pins of the test cable plug are engaged 5 Perform the BATTERY TEST procedures as specified on Page 5 of this manual All form 2 controls 1 Attach both pig tailed adapter assemblies to the specia...

Page 18: ...he MET tester 2 Connect a jumper from the left hand jack to the cabinet on the front panel of the ME control 3 Proceed to Step 1 in the Control Operation Test Ground Trip or the Minimum Trip Test Grou...

Page 19: ...15 OPERATING INSTRUCTIONS MN280067EN July 2017 Type MET electronic recloser control tester operating instructions This page intentionally left blank...

Page 20: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280067EN KA2048 229 REV02 July 2017 Eaton is a registered trademark All trademarks are property of their...

Reviews: