OPERATING INSTRUCTIONS

   MN280067EN   July 2017

Type MET electronic recloser control tester operating instructions

Operating procedures

The tester operating procedures have been grouped into:
1.  Battery tests.
2.  Control tests.
3.  Recloser test.

Each group of tests is preceded by an INITIAL CONDITIONS 

paragraph which specifies required settings for both the 

control and tester. Make sure both are set to the INITIAL 

CONDITIONS before starting. Upon completion of testing, 

return the control settings to the desired operating 

conditions before returning the control to service.

  CAUTION

To avoid electrical/ shock and possible equipment 

damage, the following grounding precautions must 

be observed .

Tester

The third-wire grounding pin of the plug on the input 

power cord must be grounded securely. Use a three-wire 

groundedoutlet receptacle which conforms to the latest 

electrical code. If a plug adapter is used, be sure to ground 

the pigtail lead securely.

Control

Make sure that the cabinet of the control is securely 

grounded to an earth ground.
If the control is equipped with an accessory which requires 

120- or 240 Vac power, make sure that the grounded leg of 

the input power source is connected to the grounded input 

terminal in the control. (Older controls without ac surge 

protection may have neither terminal grounded. Controls 

with surge modules very likely have one line grounded.) 

Verify grounding of each terminal before applying ac power. 
If a mismatch between grounds on the ME control and the 

MET tester exists when the ME control is energized with ac 

voltage, a buzzer within the MET Tester will sound. Correct 

the problem immediately before proceeding.

Testing in-service control

A recloser control can be taken out of service for testing and 

placed back into service without de-energizing the recloser 

and interrupting the system. However, during the time the 

control is out of service, system fault protection is lost.

  CAUTION

Recloser misoperation . The control must be removed 

from service prior to performing any maintenance, 

testing, or programming changes . Failure to comply 

can result in misoperation (unintentional operation) of 

the recloser . 

T216 .2

To remove the control from service

1.  Place the Ground Trip switch to “BLOCK.”
2.  Disconnect the recloser interconnecting cable at the 

receptacle on the bottom of the control cabinet.

 CAUTION

Hazardous voltage . Open CT secondaries can generate 

high voltages . Contact with CT pins of the disconnected 

cable can cause electric shock and may result in 

personal injury . Open recloser contacts and open 

disconnect switches before disconnecting  

control cable .  

T204 .3

To place the control back in service

1.  Make sure the Ground Trip switch is in BLOCK.
2.  Check that the battery is connected and all control 

settings and plugs are correct, or programmed, 

as applicable.

3.  All recloser controls other than Type Form 4A and Form 

4B: operate the Manual Control switch to CLOSE to 

make sure the control is in the home position; verify by 

placing the test switch to LOCKOUT TEST; the Lockout 

Indicator lamp should not light.

4.  Reconnect the recloser interconnecting cable to the 

receptacle on the bottom of the control cabinet.

5.  Place the Ground Trip switch to NORMAL.

Battery tests

Form 2 and Form 3 family controls only.
The left side of the tester contains the metering and 

associated switches for checking the battery and 

battery-charging circuits. The battery test cable provided 

with the tester is capable of checking battery voltage on all 

Form 3 and Form 3A controls equipped with either two- or 

three-battery test-terminal posts. For earlier Form 3 controls 

(with two-battery test-terminal posts), a special battery test 

cable—capable of checking both battery voltage and battery 

charge/discharge rates—is available as an accessory. With 

the addition of adapters to the special battery test cable, 

the battery voltage and charge/discharge rates of all Form 2 

controls (no separable battery plug and receptacle) can also 

be checked. The adapters are included with the accessory 

test cable.
Instructions for using the special battery test cable and 

adapters are included in Appendix B, page 13.

Initial conditions

Control

Battery connected and control in lockout (verify with the 

Lockout Test switch and/or Lockout Indicator, as applicable); 

battery charging circuit de-energized. Refer to the applicable 

control Installation Manual for specific information to 

de-energize the battery charging circuit.

Summary of Contents for MET

Page 1: ...Type MET electronic recloser control tester operating instructions COOPER POWER SERIES Reclosers MN280067EN Effective July 2017 Supersedes February 2001 S280 76 1...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...F LIABILITY I SAFETY FOR LIFE III SAFETY INFORMATION III Safety instructions iii SHIPMENT AND ACCEPTANCE 1 DESCRIPTION 1 SPECIFICATIONS 1 DESCRIPTION AND USE OF OPERATING CONTROLS 2 OPERATING PROCEDUR...

Page 4: ...age lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally...

Page 5: ...ecloser simulator provides a 2 1 2 cycles time delay to duplicate the interrupting time of a Type RE recloser in response to a trip signal from the control when recloser clearing time tests are being...

Page 6: ...ight Indicates an open recloser during control testing 11 Recloser simulator closed light Indicates a closed recloser during control testing 12 Timer Measures time of test 13 S 10 Timer reset button R...

Page 7: ...tional operation of the recloser T216 2 To remove the control from service 1 Place the Ground Trip switch to BLOCK 2 Disconnect the recloser interconnecting cable at the receptacle on the bottom of th...

Page 8: ...equipped with three test terminals 2 Move the manual control switch on the electronic control panel to CLOSE and release The target above the switch will show red 3 Turn Test Selector Switch S6 to DIS...

Page 9: ...RECLOSING position 3 Ground Trip switch in NORMAL position 4 Control settings programmed for desired operating conditions Tester 1 All switches and controls in their OFF or extreme counterclockwise po...

Page 10: ...CONDITIONS 2 Form 3 family controls only to prevent overshooting while raising the test current to the minimum trip level remove the timing plug from socket 1 to provide instantaneous trip 3 Check to...

Page 11: ...om the electronic control Figures 4 and 5 in Appendix A show the control response and Types RE and RVE clearing TCC curves for some common Form 3A control phase trip and ground trip timing plugs To ch...

Page 12: ...irst trip check that the control and tester settings are as specified under INITIAL CONDITIONS and proceed as follows 1 Remove the first Reclosing Interval Delay plug from the control panel and progra...

Page 13: ...h the control battery providing closing coil or closing motor energy is available at the recloser Initial conditions Control Battery connected and control in lockout verify with Lockout Test switch an...

Page 14: ...ypical phase trip TCC curves for Types RE and RVE reclosers 11 Figure 5 Typical ground trip TCC curves for Types RE and RVE reclosers 11 Table 2 Quiescent Drain of Form 2 and Form 3 Family Control Acc...

Page 15: ...KA522ME Remote minimum trip doubler 0 Supervisory contacts open 5 7 Supervisory contacts closed KA531ME Fuse elimination 0 KA533ME Dc supply adapter See KA339ME KA542ME Heater 0 KA545ME Load current i...

Page 16: ...eclose 0 KA2035ME2 Remote non reclose and remote ground trip block maintained 22 Supervisory contacts open 85 Supervisory contacts closed KA2039ME2 Recloser status 06 Recloser Open 16 Recloser Closed...

Page 17: ...three pins of the test cable plug are engaged 5 Perform the BATTERY TEST procedures as specified on Page 5 of this manual All form 2 controls 1 Attach both pig tailed adapter assemblies to the specia...

Page 18: ...he MET tester 2 Connect a jumper from the left hand jack to the cabinet on the front panel of the ME control 3 Proceed to Step 1 in the Control Operation Test Ground Trip or the Minimum Trip Test Grou...

Page 19: ...15 OPERATING INSTRUCTIONS MN280067EN July 2017 Type MET electronic recloser control tester operating instructions This page intentionally left blank...

Page 20: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280067EN KA2048 229 REV02 July 2017 Eaton is a registered trademark All trademarks are property of their...

Reviews: