OPERATING INSTRUCTIONS

   MN280067EN   July 2017

Type MET electronic recloser control tester operating instructions

To check the reclosing time, check that the control and 

tester settings are as specified under INITIAL CONDITIONS 

and proceed as follows:
1.  Set the control switch to GROUND TRIP BLOCK to 

disable the ground trip function while checking the 

reclose timing.

2.  Energize the tester by setting the ON/OFF Power 

switch S1 to ON. The green Recloser Simulator-Open 

lamp will light.

3.  Set the Ammeter Range switch S4 to the appropriate 

range for the trip current to be used.

4.  While holding the Fault Current switch S2 in CALIBRATE, 

advance the Fault Current Adjust control TR1 to 

approximately 125—150% of the minimum-trip value.

5.  Move the Manual Control switch to CLOSE and release. 

The simulator will close in approximately 3/4 second; 

green OPEN light off, red CLOSED light on.

6.  Set Time Selector switch S3 to CONTROL RECLOSE/

RESET. Place Display Mode switch, S11, to UPDATE 

and the Auto Reset switch, S12, to ON; reset the timer.

7.  Set the Fault Current switch S2 to TEST and record the 

reclosing intervals.

otee:

N

If the recloser is set for more than one fast 

operation, the reclosing time may be difficult to read, 

especially if the control is programmed with fast 

reclosing times. For easier recording of the reclosing 

intervals, set the control for 0 or 1 fast operation.

8.  Return the control and tester settings to the INITIAL 

CONDITIONS specified at the beginning of the 

CONTROL TESTS.

Reset time test

Reset time of standard Form 2 and Form 3 family controls 

with serial numbers below 26000 is measured from the 

first trip operation. However, if the control is equipped with 

the Reset-From-Successful-Reclose accessory, reset timing 

starts after any reclose where the current flowing (if any) is 

below minimum trip.
Reset time of a standard Form 3A control (serial number 

26000 or higher) and Form 4 family controls is measured 

from successful reclosing, in the same manner as the 

accessory function described above.
Different test procedures are required for checking the reset 

time of electronic controls equipped with or without the 

Reset- From-Successful-Reclose feature.

Controls which time from first trip

To check the reset time of a control which times reset 

from the first trip; check that the control and tester settings 

are as specified under INITIAL CONDITIONS and proceed 

as follows:
1.  Remove the first Reclosing Interval Delay plug from 

the control panel and program the control for all 

delayed operations.

2.  Energize the tester by setting the ON/OFF Power 

switch S1 to ON. The green Recloser Simulator-Open 

lamp will light.

3.  Set the Ammeter Range Switch S4 to the appropriate 

range for the trip current to be used.

4.  While holding the Fault Current switch S2 in 

CALIBRATE, advance the Fault Current Adjust control 

TR1 to approximately 125—150% of the  

minimum-trip value.

5.  Move the Manual Control switch to CLOSE and release. 

The simulator will close in approximately 3/4 second; 

green OPEN light off, red CLOSED light on.

6.  Set the Time Selector switch S3 to CONTROL 

RECLOSE/RESET and reset the timer.

7.  Place the Fault Current switch S2 to TEST.
8.  When the control has tripped, place the Fault Current 

switch S2 to OFF. The clock will start timing and when 

the sequence relay steps around to the first operation, 

the clock will stop and record the timing of the Reset 

Delay plug.

otee:

N

The control reset delay cannot be checked by placing 

the reset plug into the first Reclosing Interval socket. 

Proper control timing cannot be obtained under  

these conditions.

9.  Replace the Reclosing Interval Delay plug in its socket 

and return the control and tester settings to the 

INITIAL CONDITIONS specified at the beginning of the 

CONTROL TESTS.

Controls which time from successful reclose

Controls equipped with the Reset-From-Successful-Reclose 

feature; check that the control and tester settings are as 

specified under INITIAL CONDITIONS and proceed as follows:
1.  Program the electronic control for one fast and three 

delayed operations. The first Reclosing Interval Delay 

time must be programmed to have a minimum setting 

of at least two seconds.

2.  Set the control switch to GROUND TRIP BLOCK to 

disable the ground trip function while checking the 

reset time.

3.  Energize the tester by setting the ON/OFF Power 

switch S1 to ON. The green Recloser Simulator-Open 

lamp will light.

4.  Set the Time Selector switch S3 to CONTROL 

RESPONSE. Place Display Mode switch, S11, to 

UPDATE and the Auto Reset switch, S12, to ON; reset 

the timer.

5.  Form 4 family controls only; turn the display on and 

enter CODE 38. Code 38 displays the sequence state 

of the control, “0” being home.

6.  Set the Ammeter Range switch S4 to the appropriate 

range for the trip current to be used.

Summary of Contents for MET

Page 1: ...Type MET electronic recloser control tester operating instructions COOPER POWER SERIES Reclosers MN280067EN Effective July 2017 Supersedes February 2001 S280 76 1...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...F LIABILITY I SAFETY FOR LIFE III SAFETY INFORMATION III Safety instructions iii SHIPMENT AND ACCEPTANCE 1 DESCRIPTION 1 SPECIFICATIONS 1 DESCRIPTION AND USE OF OPERATING CONTROLS 2 OPERATING PROCEDUR...

Page 4: ...age lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally...

Page 5: ...ecloser simulator provides a 2 1 2 cycles time delay to duplicate the interrupting time of a Type RE recloser in response to a trip signal from the control when recloser clearing time tests are being...

Page 6: ...ight Indicates an open recloser during control testing 11 Recloser simulator closed light Indicates a closed recloser during control testing 12 Timer Measures time of test 13 S 10 Timer reset button R...

Page 7: ...tional operation of the recloser T216 2 To remove the control from service 1 Place the Ground Trip switch to BLOCK 2 Disconnect the recloser interconnecting cable at the receptacle on the bottom of th...

Page 8: ...equipped with three test terminals 2 Move the manual control switch on the electronic control panel to CLOSE and release The target above the switch will show red 3 Turn Test Selector Switch S6 to DIS...

Page 9: ...RECLOSING position 3 Ground Trip switch in NORMAL position 4 Control settings programmed for desired operating conditions Tester 1 All switches and controls in their OFF or extreme counterclockwise po...

Page 10: ...CONDITIONS 2 Form 3 family controls only to prevent overshooting while raising the test current to the minimum trip level remove the timing plug from socket 1 to provide instantaneous trip 3 Check to...

Page 11: ...om the electronic control Figures 4 and 5 in Appendix A show the control response and Types RE and RVE clearing TCC curves for some common Form 3A control phase trip and ground trip timing plugs To ch...

Page 12: ...irst trip check that the control and tester settings are as specified under INITIAL CONDITIONS and proceed as follows 1 Remove the first Reclosing Interval Delay plug from the control panel and progra...

Page 13: ...h the control battery providing closing coil or closing motor energy is available at the recloser Initial conditions Control Battery connected and control in lockout verify with Lockout Test switch an...

Page 14: ...ypical phase trip TCC curves for Types RE and RVE reclosers 11 Figure 5 Typical ground trip TCC curves for Types RE and RVE reclosers 11 Table 2 Quiescent Drain of Form 2 and Form 3 Family Control Acc...

Page 15: ...KA522ME Remote minimum trip doubler 0 Supervisory contacts open 5 7 Supervisory contacts closed KA531ME Fuse elimination 0 KA533ME Dc supply adapter See KA339ME KA542ME Heater 0 KA545ME Load current i...

Page 16: ...eclose 0 KA2035ME2 Remote non reclose and remote ground trip block maintained 22 Supervisory contacts open 85 Supervisory contacts closed KA2039ME2 Recloser status 06 Recloser Open 16 Recloser Closed...

Page 17: ...three pins of the test cable plug are engaged 5 Perform the BATTERY TEST procedures as specified on Page 5 of this manual All form 2 controls 1 Attach both pig tailed adapter assemblies to the specia...

Page 18: ...he MET tester 2 Connect a jumper from the left hand jack to the cabinet on the front panel of the ME control 3 Proceed to Step 1 in the Control Operation Test Ground Trip or the Minimum Trip Test Grou...

Page 19: ...15 OPERATING INSTRUCTIONS MN280067EN July 2017 Type MET electronic recloser control tester operating instructions This page intentionally left blank...

Page 20: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280067EN KA2048 229 REV02 July 2017 Eaton is a registered trademark All trademarks are property of their...

Reviews: