OPERATING INSTRUCTIONS

   MN280067EN   July 2017

Type MET electronic recloser control tester operating instructions

Shipment and acceptance

This test set is completely assembled. inspected, adjusted, 

and tested at the factory. It is in good condition when 

accepted by the carrier for shipment. Upon receipt, inspect 

the test set thoroughly for damage and loss of parts 

incurred during shipment. If damage or loss is discovered, 

file a claim immediately with the carrier.

Description

The Eaton Cooper Power series Type MET electronic 

recloser control tester (Figure 1) is designed specifically for 

testing Type ME Form 2, Form 3, Form 3A, Form 4A and 

Form 4C controls. The tester has the capability to check 

the following:
1.  Battery voltage (load and no load).
2.  Battery charge and discharge rates.
3.  Minimum-trip current, phase and ground (low range to 

5 amp ground).

4.  Operating sequence.
5.  Control response time (phase and ground trip).
6.  Reclosing time.
7.  Reset time.
8.  Electrical operation of recloser.
9.  Various accessory functions through simulation of the 

conditions under which they operate.

The self-contained unit is compactly packaged in a sturdy, 

weather-proof carrying case with a detachable front cover. 

Cables for connecting the recloser, electronic control, and 

control battery to the tester are supplied with the tester and 

stored in the carrying case along with spare fuses and bulbs 

for panel lights. No other external equipment or accessories 

are required when using the tester.
The tester can check operation of the electronic recloser 

control and also can check the electrical operation of 

the recloser (provided reclosing power is available at the 

recloser). However, the control cannot operate the recloser 

through the tester.
A recloser-simulator circuit is built into the tester to simulate 

recloser operation (indicated by red and green lights on 

the tester panel) and to simulate the response time of the 

recloser mechanism to trip and close signals. The recloser 

simulator provides a 2-1/2-cycles time delay to duplicate 

the interrupting time of a Type RE recloser in response to 

a trip signal from the control when recloser clearing time 

tests are being conducted. It also provides a time delay 

of approximately 30 cycles to duplicate the response time 

of a Type RE or WE recloser to a reclosing signal from the 

control when reclosing time tests are being conducted.

Specifications

Input

115 Vac, 50/60 Hz, single phase (fused for two amp) with 

15-ft power cord and a three wire grounding plug.
240 Vac 50/60 Hz, single phase (fused for one amp) with 15-ft 

power cord with no plug attached, is available as an accessory.

Output

0—3000 mA continuously adjustable from front panel of tester.

Instrumentation

1.  DC METER

Edgewise panel meter with two-in. horizontal scale; 

accuracy ±5% full scale; panel switched ranges: 

0—4/40 mA, 0—40 V.

2.  AC METER

Edgewise panel meter with two-in. horizontal scale; 

accuracy ±5% full scale; panel switched ranges: 

0—30/100/ 1000/3000 mA.

otee:

N

Jacks on the tester panel provide the means for 

connecting an external ammeter into the circuit. They 

may be used for calibrating the internal meter or it 

different scales or greater accuracy is desired.

3.  TIMER

LCD readout digital clock timer, 000.000 to 999.999 

seconds in 0.001-second increments; with manual and 

automatic reset; accuracy ±0.001% ±1 digit.

Interconnecting cables

1.  15-ft cable for connecting electronic control to tester.
2.  15-ft extension cable for connecting end of recloser 

cable to tester.

3.  15-ft cable for directly connecting control-panel battery 

terminals to tester.

otee:

N

Connector terminations on all cables are polarized to 

assure proper interconnection An internal buzzer will 

sound it a mismatch between grounds on the ME 

control and the MET tester exists.

AC power cord

15-ft three-wire power cord with groundable power plug

Carrying case

Tester is packaged in a sturdy Formica covered carrying case 

with removable front cover; has provisions for storing power 

cord, interconnecting cables. and spare fuses and bulbs.

Dimension

9-1/2 in. high, 21 in. wide, 13-1/4 in. deep overall.

Weight (approximately .)

Net 33 Ib; shipping 37 Ib.

Summary of Contents for MET

Page 1: ...Type MET electronic recloser control tester operating instructions COOPER POWER SERIES Reclosers MN280067EN Effective July 2017 Supersedes February 2001 S280 76 1...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...F LIABILITY I SAFETY FOR LIFE III SAFETY INFORMATION III Safety instructions iii SHIPMENT AND ACCEPTANCE 1 DESCRIPTION 1 SPECIFICATIONS 1 DESCRIPTION AND USE OF OPERATING CONTROLS 2 OPERATING PROCEDUR...

Page 4: ...age lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally...

Page 5: ...ecloser simulator provides a 2 1 2 cycles time delay to duplicate the interrupting time of a Type RE recloser in response to a trip signal from the control when recloser clearing time tests are being...

Page 6: ...ight Indicates an open recloser during control testing 11 Recloser simulator closed light Indicates a closed recloser during control testing 12 Timer Measures time of test 13 S 10 Timer reset button R...

Page 7: ...tional operation of the recloser T216 2 To remove the control from service 1 Place the Ground Trip switch to BLOCK 2 Disconnect the recloser interconnecting cable at the receptacle on the bottom of th...

Page 8: ...equipped with three test terminals 2 Move the manual control switch on the electronic control panel to CLOSE and release The target above the switch will show red 3 Turn Test Selector Switch S6 to DIS...

Page 9: ...RECLOSING position 3 Ground Trip switch in NORMAL position 4 Control settings programmed for desired operating conditions Tester 1 All switches and controls in their OFF or extreme counterclockwise po...

Page 10: ...CONDITIONS 2 Form 3 family controls only to prevent overshooting while raising the test current to the minimum trip level remove the timing plug from socket 1 to provide instantaneous trip 3 Check to...

Page 11: ...om the electronic control Figures 4 and 5 in Appendix A show the control response and Types RE and RVE clearing TCC curves for some common Form 3A control phase trip and ground trip timing plugs To ch...

Page 12: ...irst trip check that the control and tester settings are as specified under INITIAL CONDITIONS and proceed as follows 1 Remove the first Reclosing Interval Delay plug from the control panel and progra...

Page 13: ...h the control battery providing closing coil or closing motor energy is available at the recloser Initial conditions Control Battery connected and control in lockout verify with Lockout Test switch an...

Page 14: ...ypical phase trip TCC curves for Types RE and RVE reclosers 11 Figure 5 Typical ground trip TCC curves for Types RE and RVE reclosers 11 Table 2 Quiescent Drain of Form 2 and Form 3 Family Control Acc...

Page 15: ...KA522ME Remote minimum trip doubler 0 Supervisory contacts open 5 7 Supervisory contacts closed KA531ME Fuse elimination 0 KA533ME Dc supply adapter See KA339ME KA542ME Heater 0 KA545ME Load current i...

Page 16: ...eclose 0 KA2035ME2 Remote non reclose and remote ground trip block maintained 22 Supervisory contacts open 85 Supervisory contacts closed KA2039ME2 Recloser status 06 Recloser Open 16 Recloser Closed...

Page 17: ...three pins of the test cable plug are engaged 5 Perform the BATTERY TEST procedures as specified on Page 5 of this manual All form 2 controls 1 Attach both pig tailed adapter assemblies to the specia...

Page 18: ...he MET tester 2 Connect a jumper from the left hand jack to the cabinet on the front panel of the ME control 3 Proceed to Step 1 in the Control Operation Test Ground Trip or the Minimum Trip Test Grou...

Page 19: ...15 OPERATING INSTRUCTIONS MN280067EN July 2017 Type MET electronic recloser control tester operating instructions This page intentionally left blank...

Page 20: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280067EN KA2048 229 REV02 July 2017 Eaton is a registered trademark All trademarks are property of their...