7

OPERATING INSTRUCTIONS

   MN280067EN   July 2017

Type MET electronic recloser control tester operating instructions

3.  Form 3 family controls only: To prevent overshooting 

while raising the test current to the minimum-trip 

level, remove the timing plug from Socket 1 to provide 

instantaneous trip.

4.  Make sure the control is programmed for at least one 

fast ground trip operation.

5.  Set control switch to NON-RECLOSING to provide 

oneshot- to-lockout operation.

6.  Energize the tester by setting the ON/OFF Power 

switch S1 to ON. The green Recloser Simulator-Open 

lamp will light.

7.  Set the Ammeter Range switch S4 to the appropriate 

range for the expected minimum-trip current.

8.  Set the Low Ground Trip-Normal switch S9 to normal 

unless the control is programmed to trip at a below 

10-amp; then place switch in Low Ground Trip position.

9.  Move the Manual Control switch to CLOSE and release. 

The simulator will close in approximately 3/4 second; 

green OPEN light off, red CLOSED light on.

10.  Apply fault current.

A.  Form 2 and Form 3 family controls: Set Fault 

Current switch S2 to TEST and advance 

Fault-Current Adjust control TR1 from 0 while 

observing the ac Ammeter reading.

B.  Form 4 family controls: Set Fault Current switch  

S2 to TEST and advance Fault-Current Adjust 

control TR1 from 0 while observing the control’s 

Current Above Minimum Trip indicator, note the 

current recorded by the Ac Ammeter at the point 

where the indicator displays.

otee:

N

For Form 3 family controls equipped with the 

Low-Current Ground-Trip accessory, the 5.8-amp 

minimum-trip resistor should trip at an equivalent 

test current of 5.0 mA and the 10-amp resistor at 

an equivalent test current of 9.2 mA when the Low 

Ground Trip-Normal switch S9 is in the Low Ground 

Trip position.

11.  Return the control and tester settings to INITIAL 

CONDITIONS; Form 3 family controls, remove the 

shorting jumper from across the A-phase-trip resistor; 

Form 4 family controls, re-program the phase minimum 

trip level to its original level.

TCC check

Either the control-response time or the recloser-clearing 

time can be checked by setting the Time Selector switch 

to the appropriate position. In the RECLOSER CLEARING 

position, the trip time will include a delay of approximately 

2-1/2 cycles, the time it takes a Type RE or RVE recloser to 

respond to the trip signal from the electronic control. 
Figures 4 and 5, in Appendix A, show the control response 

and Types RE and RVE clearing TCC curves for some 

common Form 3A control phase-trip- and ground-trip-timing 

plugs. To check the time-current characteristics, check 

that the control and tester settings are as specified under 

INITIAL CONDITIONS and proceed as follows:
1.  Set the control switch to GROUND TRIP BLOCK to 

disable the ground trip function while checking the 

phase trip-timing plugs.

2.  Set the Time Selector switch S3 to either CONTROL 

RESPONSE or RECLOSER CLEARING as appropriate. 

Place Display Mode switch, S11, to UPDATE and the 

Auto Reset switch, S12, to ON.

3.  Energize the tester by setting the ON/OFF Power 

switch S1 to ON. The green Recloser Simulator-Open 

lamp will light.

4.  Set the Ammeter Range switch S4 to the appropriate 

range for the current at the predetermined test point on 

the TCC curve.

5.  While holding the Fault Current switch S2 in 

CALIBRATE, advance the Fault Current Adjust control 

TR1 until the ammeter indicates the desired value 

(minimum trip level, or greater).

6.  Move the Manual Control switch to CLOSE and release. 

The simulator will close in approximately 3/4 second; 

green OPEN light off, red CLOSED light on.

7.  Reset the timer.
8.  Set the Fault Current switch S2 to TEST and record the 

response or clearing times of the phase-trip-timing curve.

9.  Set the Fault Current switch S2 to OFF and repeat 

steps 6, 7, and 8 with Phase Selector switch S5 set at 

B and at C.

10.  Return the Phase Selector switch S5 to A, control 

Ground Trip switch to NORMAL.

11.  Control settings.

A.  A. Form 2, Form 3 and Form 3A controls: place a 

shorting jumper across the A phase-trip resistor 

to disable the phase trip function while checking 

the ground trip operation, and check that Phase 

Selector switch S5 is also set to A.

B.  B. Form 4A and Form 4B controls: program the 

phase minimum trip level to, at minimum, 2 times 

(200%) the ground minimum trip level.

12.  Repeat steps 4 through 8 and record the response or 

clear-ing times of the ground-trip-timing plugs.

13.  Return the control and tester settings to INITIAL 

CONDITIONS; Form 3 family controls, remove the 

shorting jumper from across the A-phase-trip resistor; 

Form 4 family controls, re-program the phase minimum 

trip level to its original level.

Reclosing time test

The recloser simulator has a built-in time delay of 

approximately 30 cycles before the reclosing signal from 

the electronic control is implemented. This simulates the 

mechanical operating time of the Types RE and WE reclosers.

Summary of Contents for MET

Page 1: ...Type MET electronic recloser control tester operating instructions COOPER POWER SERIES Reclosers MN280067EN Effective July 2017 Supersedes February 2001 S280 76 1...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...F LIABILITY I SAFETY FOR LIFE III SAFETY INFORMATION III Safety instructions iii SHIPMENT AND ACCEPTANCE 1 DESCRIPTION 1 SPECIFICATIONS 1 DESCRIPTION AND USE OF OPERATING CONTROLS 2 OPERATING PROCEDUR...

Page 4: ...age lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally...

Page 5: ...ecloser simulator provides a 2 1 2 cycles time delay to duplicate the interrupting time of a Type RE recloser in response to a trip signal from the control when recloser clearing time tests are being...

Page 6: ...ight Indicates an open recloser during control testing 11 Recloser simulator closed light Indicates a closed recloser during control testing 12 Timer Measures time of test 13 S 10 Timer reset button R...

Page 7: ...tional operation of the recloser T216 2 To remove the control from service 1 Place the Ground Trip switch to BLOCK 2 Disconnect the recloser interconnecting cable at the receptacle on the bottom of th...

Page 8: ...equipped with three test terminals 2 Move the manual control switch on the electronic control panel to CLOSE and release The target above the switch will show red 3 Turn Test Selector Switch S6 to DIS...

Page 9: ...RECLOSING position 3 Ground Trip switch in NORMAL position 4 Control settings programmed for desired operating conditions Tester 1 All switches and controls in their OFF or extreme counterclockwise po...

Page 10: ...CONDITIONS 2 Form 3 family controls only to prevent overshooting while raising the test current to the minimum trip level remove the timing plug from socket 1 to provide instantaneous trip 3 Check to...

Page 11: ...om the electronic control Figures 4 and 5 in Appendix A show the control response and Types RE and RVE clearing TCC curves for some common Form 3A control phase trip and ground trip timing plugs To ch...

Page 12: ...irst trip check that the control and tester settings are as specified under INITIAL CONDITIONS and proceed as follows 1 Remove the first Reclosing Interval Delay plug from the control panel and progra...

Page 13: ...h the control battery providing closing coil or closing motor energy is available at the recloser Initial conditions Control Battery connected and control in lockout verify with Lockout Test switch an...

Page 14: ...ypical phase trip TCC curves for Types RE and RVE reclosers 11 Figure 5 Typical ground trip TCC curves for Types RE and RVE reclosers 11 Table 2 Quiescent Drain of Form 2 and Form 3 Family Control Acc...

Page 15: ...KA522ME Remote minimum trip doubler 0 Supervisory contacts open 5 7 Supervisory contacts closed KA531ME Fuse elimination 0 KA533ME Dc supply adapter See KA339ME KA542ME Heater 0 KA545ME Load current i...

Page 16: ...eclose 0 KA2035ME2 Remote non reclose and remote ground trip block maintained 22 Supervisory contacts open 85 Supervisory contacts closed KA2039ME2 Recloser status 06 Recloser Open 16 Recloser Closed...

Page 17: ...three pins of the test cable plug are engaged 5 Perform the BATTERY TEST procedures as specified on Page 5 of this manual All form 2 controls 1 Attach both pig tailed adapter assemblies to the specia...

Page 18: ...he MET tester 2 Connect a jumper from the left hand jack to the cabinet on the front panel of the ME control 3 Proceed to Step 1 in the Control Operation Test Ground Trip or the Minimum Trip Test Grou...

Page 19: ...15 OPERATING INSTRUCTIONS MN280067EN July 2017 Type MET electronic recloser control tester operating instructions This page intentionally left blank...

Page 20: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280067EN KA2048 229 REV02 July 2017 Eaton is a registered trademark All trademarks are property of their...

Reviews: