Magnefix MD4
991.184 G01 03
89
4. Push the high-speed earthing equipment into the
switch-on equipment holder until it engages in the
spring clamp.
4
5. Push the earthing cap as far as possible into the
central opening in the fixed component of the switch
equipment, making sure that the protruding part of the
switch-on equipment (A) is at the left.
5
6. Push in the interlock pins on the switch grip to release
them and then push the switch-on equipment forcefully
in the direction of the switchgear so that the closing
springs of the switch-on equipment are released and
the earthing equipment is activated.
The design of the earthing cap causes it to become
interlocked in the fixed component.
7. Tug the switch-on equipment briefly to remove it from
the earthing cap.
6