15. Close the filling hose using the shut-off ring.
15
16. Reduce the pressure on the can by completely
opening the valve.
17. Undo the hose clip and remove the can from the filling
hose.
18. Hold the can in such a way that the grease in the filling
hose cannot come into contact with the valve, to avoid
clogging.
16 .. 18
19. Remove the filling hose from the cable box once the
grease in the cable box has cooled down and
immediately put your thumb on the opening. This is
necessary as the grease in the cable box is under
pressure.
Pinch the filling hose to remove grease residues.
20. Fit the rubber sealing and push it into the opening of
the cable box, while rotating it. Make sure that the
edge snaps behind the wall of the cable box.
21. Fit the nylon locking pin. There must not be any grease
in the cavity in the rubber sealing.
22. Allow the grease in the can to cool down and place the
transport/storage cover on the can using the fixinig
ring. Remaining grease can be re-used when the can
is not damaged.