![background image](http://html1.mh-extra.com/html/eaton/iq-200/iq-200_installation-operation-and-maintenance-manual_3830378020.webp)
TD 17558
Page 13
Effective 3/98
3.2.1 Mounting the IQ 200 Modules as a Single Unit
Using the screws provided, attach the supplied DIN rail to the back of the IQ 200
Display. Use the screws provided with the IQ 200 Base Module to attach the
supplied DIN clip to the front face of the IQ 200 Base Module.
Cut a ¼ DIN (92mm x 92mm) access cutout in the switchgear door or other panel
where the IQ 200 is to be mounted as shown in figure 3.1. Install the IQ 200 Display
Module as shown in figure 3.1, following these steps:
•
Install the supplied gasket
when using in NEMA 12
applications.
•
Slide the supplied gasket over
the rear of the IQ 200 Display
Module until it is flush with the
rear of the outer bezel.
•
Insert the IQ 200 Display
Module with gasket installed
into the cutout.
•
Slide the 4 supplied locking
bars into the 4 slots in the top,
bottom, and sides at the rear of
the IQ 200 Display Module
Figure 3.1 Securing the IQ 200 Display
Module
•
Insert and tighten the supplied thumbscrews to secure the IQ 200 Display Module
in place.
•
Connect the IQ 200 Base Module to the IQ 200 Display Module using the DIN rail
and clip, as shown in figure 3.2.
Connect the IQ 200 Display
Module to the IQ 200 Base
Module by inserting one end of the
1 foot long Category 5 cable into
the port on the IQ 200 Display
Module, and the other end into the
DISPLAY port on the IQ 200 Base
Module.
Do not route the Category
5 cable in the same enclosure or
cable tray as 600V system wiring
.
Proceed to
section 3.3, Wiring.
Figure 3.2 Mounting the IQ 200 Base
Module to the IQ 200 Display Module
3.2.2 Mounting the IQ 200 Display and Base Modules Separately
In
all
instances where the IQ 200 Base Module is mounted remotely, the IQ 200
Display Module Chassis
must
be connected to earth ground.