EATON ELECTRICAL
33
Predictive Diagnostics
3 Startup
3.1 Setting InsulGard
3.1.1 General
InsulGard allows for device setting from keypad and via RS-485/232 interface from PC using InsulGard software. (For
software setting please refer to Software manual.)
Setting the device from PC is easier, but there are some settings available ONLY from the keypad. These are parameters
or procedures that must be set at device commissioning time or at factory calibration:
•
Device address on a network
•
Automatic Phase Shift detection (Learn more in the Appendix 2 before starting this).
•
Transmission Baud Rate
•
Temperature channel calibration (Normally calibrated in the factory, if RTD type information is provided.)
•
Voltage channel calibration
•
Current channel calibration
3.1.2 Quick Start Up
Normally, InsulGard preset at the factory for particular application. The setup procedure below is a minimum
procedure that is required for setting to monitoring. Specific applications might require some additional
procedures. The sequence of the steps is most optimal. Try to follow the sequence.
Once InsulGard is installed, all signals are connected and equipment is powered up, What are the most critical
parameters to at commissioning? The following description attempts to present an order of the device setting. For full