EATON ELECTRICAL
34
Predictive Diagnostics
description of setup options refer to sections below and the software manual. Some of setting procedures are skipped,
instead, default factory settings are used. The following procedure assumes the most difficult manual setup. If set from a
PC, many settings can be combined into one setup command. Refer to “InsulGard Software Manual”.
You can print the following table below and check that the procedures are completed.
Quick Startup table
Parameter or
Procedure
Description or Notes
Setup keys
√
√
Clear All
Memory
This is a very sensitive procedure. Performing it clears
all device data memory. This is necessary at the
beginning of PD monitoring on a NEW object.
Press simultaneously
keys.
CLEArALL
will appear. To confirm press
Enter
, to exit press
Esc
.
If confirmed,
CLEArinG
will appear. Wait until
CLEArEd
appears. The
memory is clear.
Press
Esc
.
Enter Setup
Enter appropriate password and enter setup.
Your password is
5421
Press “
Set
” key.
PSd-____
will appear on the display. A correct
password must be entered, in order to enter the setup mode. Using
keys enter password and press
ENTER
. Wait for about 20sec.
The first option to appear is the date/time setup. Use the right and left
arrow keys (
) to scroll the setup parameters.
Date & Time
Note that IG with Firmware version 2.0 and later
performs data continuity check while setting date and
time. Setting data and time earlier then preexisting data
causes ALARM status.
Scroll setup parameters until
d-XX.XX.XX
appears. Press
Enter
. Active
digits will start flashing. Use
keys to select the desired numeral. Use
keys to activate the next (previous) segment of the display.
When done, press
Enter
.
In the firmware versions 2.0 and later, If DATE that is set is earlier then
preexisting data IG will prompt for clearing data that is later than date is
set.
The prompt is
EditArCH
If Enter is pressed all later data will be erased,
if Cancel is pressed new date will be set without data erasing and then in
normal mode
CLOCHErr
will be displayed.
Set time similarly to date setting manner.
Device
Address
Device is shipped with the address 01, if other was
not specified or manufacturer does not have data on
previously installed in this location devices. If the
Scroll setup parameters until
ndEVICE
appears.
Press
Enter
.
ndEV-001
will appear. Use
keys to set the required
device address. Do not exceed 231. When done, press
Enter
.