background image

4

iLumin Plus

www.eaton.com/lightingsystems

General Information

Cabinet Dimensions

ILS-*: Small Enclosure  (two DIN rail modules)

ILM-*: Medium Enclosure (four DIN rail modules, plus 
optional ethernet)

ILL-*: Large Enclosure (eight DIN rail modules, plus optional 
ethernet)

Mounting the Enclosure

The iLumin Plus modules consist of an enclosure with 

interior DIN rail modules.  Interior DIN rail modules include:
•  SCMR1220-NA:  twelve 20A latching relays
•  SCMH1200-NA:  twelve 0-10V dimmers
•  SCMD4: four two wire addressable buses
•  EG2: Ethernet gateway

•  CR1-RJ: PC network connection

Note:

 Ensure at least three(3) inches of air space around the 

iLumin Plus enclosure.

Location and Spacing

The iLumin Plus models are all fully convection cooled; 

therefore it is vitally important to ensure that each unit is 

installed in a ventilated location that permits sufficient airflow 

and provides the correct operating conditions.
The cabinets do not contain fans.  Allowing airflow around 

the panel will enhance the reliability and longevity of 

all models. Locating panels away from heat generating 

equipment will also benefit long term reliability. Also ensure 

that  the  stated ambient atmosphere requirements are not 

exceeded.

Ambient Atmosphere Requirements

Temperature 32° F to 104° F (0° C to +40° C)
Humidity 0 to 95% non-condensing

Mounting Considerations

•  A minimum of 14 inches (360 mm) must be maintained 

from the front of the chassis to any other components or 

walls. Please make sure to check and follow local code 

requirements if additional clearance is needed per code in 

your area

•  Allow adequate space for future maintenance of the unit. 

Do not install in a location that will later be difficult to 

access

•  The iLumin Plus panel is designed to be mounted vertically
•  Use suitable conduits and couplers to link the raceways to 

the controller chassis

35.54

25.73

LARGE

35.29

35.54

6.07

25.15

25.67

25.493

25.34

MEDIUM

25.12

6.06

25.12

25.34

SMALL

14.56

12.22

14.00

3.56

12.00

Summary of Contents for iLumin Plus

Page 1: ...large units Failure to comply with these instructions may result in serious injury including death and property damage WARNING DISCLAIMER OF LIABILITY Eaton assumes no liability for damages or losses...

Page 2: ...ow voltage Input Class 2 Low voltage Input Installation steps 1 Mount enclosure 2 Connect panel power 3 Connect relay wiring 4 Connect 0 10V dimmer wiring 5 Connect 2 wire data bus wiring 6 Connect iL...

Page 3: ...nd discard before field wiring This includes cardboard spacers in small cabinets and plastic tie wraps used on all SCMR relay modules SCMR Branch Circuit OCP SCCR NOTE Cabinets containing SCMR modules...

Page 4: ...ct operating conditions The cabinets do not contain fans Allowing airflow around the panel will enhance the reliability and longevity of all models Locating panels away from heat generating equipment...

Page 5: ...l cabinets have been designed to provide a clear layout and logical progression for all power circuits The main supply conductors enter at the top panel Input power is then fed to the modules inside t...

Page 6: ...on the interior DIN rail per the order specifications Each 0 10V dimmer requires a corresponding relay from the SCMR1220 NA to turn the lighting load ON OFF This mapping is performed during programmi...

Page 7: ...R1 RJ PC connection device A PC can be connected to the iLumin Plus panel using the SW2 cable kit plugging into the RJ port on the CR1 RJ If this iLumin Plus panel is connected to the lighting network...

Page 8: ...to access the lighting network via the buildign LAN or VLAN Note The EG2 can be use as a LAN bridge to connect different building lighting networks as a single lighting network over the building LAN...

Page 9: ...de taille La d sob issance aux instructions suivantes repr sente un risque de blessures y compris la mort et de dommages mat riels AVERTISSEMENT EXON RATION DE RESPONSABILIT Eaton n assume aucune resp...

Page 10: ...limentation du panneau 3 Raccordement du c blage de relais 4 Raccordement du c blage du gradateur de 0 10 V 5 Raccordement des deux c bles de conducteur du bus de donn es 6 Raccordement du c blage du...

Page 11: ...que REMARQUE SUR LA PROTECTION CONTRE LES SURINTENSIT S et LE COURANT DE COURT CIRCUIT NOMINAL du circuit r sonance coupl e magn tique Les armoires qui contiennent les modules r sonance coupl e magn t...

Page 12: ...armoires ne comportent pas de ventilateur Permettre une circulation d air autour du panneau am liorera la fiabilit et la dur e de vie de tous les mod les Installer les panneaux loin du mat riel qui g...

Page 13: ...et une progression logique pour tous les circuits d alimentation Les conducteurs de l alimentation principale p n trent dans le haut du panneau La puissance d entr e est ensuite aliment e vers les mo...

Page 14: ...Humidit entre 0 et 95 sans condensation Les modules de gradation SCMH1200 NA sont pr alablement mont s l int rieur du rail DIN conform ment aux sp cifications de la commande Chaque gradateur de 0 10 V...

Page 15: ...ge Les moyens et les grands panneaux iLumin Plus comprennent le dispositifs de connexion pour ordinateur CR1 RJ Un ordinateur peut tre raccord au panneau iLumin Plus l aide de la trousse de c bles SW2...

Page 16: ...suite iCANsoft pour le processus de configuration Connexion Ethernet Wiring Information Connection RJ45 connector Use Category 5 or Category 6 cable minimum Connect Connect to building LAN or VLAN for...

Page 17: ...e estas instrucciones puede provocar lesiones graves incluida la muerte y da os a la propiedad ADVERTENCIA RENUNCIA DE RESPONSABILIDAD Eaton no asume ninguna responsabilidad por da os o p rdidas de ni...

Page 18: ...te el recinto 2 Conecte la alimentaci n del panel 3 Conecte el cableado del rel 4 Conecte el cableado del atenuador de 0 10V 5 Conecte el cableado del bus de datos de 2 cables 6 Conecte el cableado de...

Page 19: ...e separadores de cart n en peque os armarios y envolturas de pl stico que se usan en todos los m dulos SCMR rel s Circuito derivado SCMR OCP y SCCR NOTA Los armarios que contienen m dulos SCMR NO incl...

Page 20: ...miento correctas Los armarios no contienen ventiladores Permitir el flujo de aire alrededor del panel mejorar la confiabilidad y longevidad de todos los modelos La ubicaci n de paneles lejos de equipo...

Page 21: ...ise ados para proporcionar un dise o claro y una progresi n l gica para todos los circuitos de alimentaci n Los conductores principales de suministro ingresan en el panel superior La corriente de entr...

Page 22: ...n Los m dulos de atenuaci n SCMH1200 NA se premontar n en el riel DIN interior seg n las especificaciones del pedido Cada atenuador de 0 10V requiere un rel correspondiente del SCMR1220 NA para ENCEND...

Page 23: ...4 Conect ndose a la red de iluminaci n Los paneles iLumin Plus medianos y grandes incluyen el dispositivo de conexi n CR1 RJ PC Se puede conectar una PC al panel de iLumin Plus utilizando el kit de ca...

Page 24: ...Category 6 cable minimum Connect Connect to building LAN or VLAN for lighting network access Note The EG2 can be used to access the lighting network via the buildign LAN or VLAN Note The EG2 can be u...

Reviews: