background image

6

iLumin Plus

www.eaton.com/lightingsystems

Connecting the Supply

The suggested entry  point for the  supply  wiring is via 
the  rightmost knockout on the  top panel  of the  chassis. 
This provides immediate access to the  circuit breaker that 
supplies the modules with power. Use  a suitable conduit  
and coupler  to feed  the source wiring safely  into the  
chassis.

See  the  diagram  below  for connection details. The main 
earth  terminal  is located near  to the  neutral  lug. The earth 
connection is bonded to the  main backplane of the  chassis 
and the  outer  panels.

Please consult the  image  below  for details  about  the 
maximum permissible supply  wire gauges for the  various 
controller  models.

Connecting Relay Loads

The relay modules (SCMR1220-NA) will be pre-mounted 

on the interior DIN rail per the order specifications. Unless 

otherwise specified, latching relays (single pole) will be 

provided for connection to lighting loads. 
Prior to relay connection, test the load directly connected to 

the branch circuit breaker to verify that there are no shorts. 

Remove all wire cuttings from the enclosure.
Relays are numbered 1-12 on each SCMR1220-NA module.  

Using the iLumin Plus programming software each relay can 

be programmed to meet control requirements. The table 

below indicates the minimum wires size to be used with 

various load currents.

Minimum AWG

For loads up to

10

20A

12

16A

14

12A

Use 75C wire insulation minimum. Use copper conductors only.

20A max load per channel

192A max load per SCMR1220-NA

Connecting 0-10V Dimmer Loads

Temperature 32° F to 104° F (0° C to +40° C)
Humidity 0 to 95% non-condensing
The dimmer modules (SCMH1200-NA) will be pre-mounted 

on the interior DIN rail per the order specifications. Each 

0-10V dimmer requires a corresponding relay from the 

SCMR1220-NA to turn the lighting load ON/OFF. This 

mapping is performed during programming.

Prior to dimmer connection, test each load to verify there 

are no shorts and 0-10V polarity is correct.  Remove all wire 

cuttings from the enclosure.
0-10V dimmers are number 1-12 on each SCMH1200-NA 

module.  Each 0-10V dimmer can be programmed to be 

either source or sink the 10VDC, by default the dimmers are 

sink type.

Relay Load Wiring Detail

Twelve: 20A Latching Relays

0-10V Dimmer Wiring Detail

Twelve: 0-10V Dimmers

Ground

Line In
Neutral

Wiring Information:

Strip wire:  

1

2

" to 

5

8

"

Wire size: 10-12AWG 

   Solid/stranded copper only

   

*Note:  Bring dedicated circuit to power 

iLumin Plus lighting panel.  Main power circuit 

should not also power lighting.

iLumin Plus is pre-wired to power all modules 

once main power is connected and energized.

Wiring Information:

Strip wire:  

1

2

" to 

5

8

"

Wire size: 10-14AWG 

   Solid/stranded copper only

   Use 75C wire insulation minimum

Load:

   120-277VAC 20A per relay 

    Mag., Res, General Purpose

    120V 20A Tungsten

    120V 16A LED Ballast

    277V 16A LED Ballast

   

   Do not exceed 192A per module

   Relay screw torque 1.1Nm

*Note:  Branch Circuit over current protection 

by others.  Each relay has a 5K SCCR unless 

protected by another device.

Class 1 Field Relay Terminals & Loads

20A max 10AWG min wire

16A max 12AWG min wire

12A max 14AWG min wire

Load Out

Line In

Class 2

Class 2

Class 2

Purple

Gray

Wiring Information:

Strip wire:  

1

2

" to 

5

8

"

Wire size: 18-14AWG 

   Solid/stranded copper only

   Dimmer screw torque 1.1Nm

   Suitable for Class 1 and Class 2 

   wiring per NFPA 70

Load:

   100mA source/sink per channel

   0-10VDC isolated (40 uA max per 

   circuit leakage to line)

*Note: Requires a relay (SCMR1220-NA) for 

load On/Off capabilities.

   

Class 2

Class 2

Summary of Contents for iLumin Plus

Page 1: ...large units Failure to comply with these instructions may result in serious injury including death and property damage WARNING DISCLAIMER OF LIABILITY Eaton assumes no liability for damages or losses...

Page 2: ...ow voltage Input Class 2 Low voltage Input Installation steps 1 Mount enclosure 2 Connect panel power 3 Connect relay wiring 4 Connect 0 10V dimmer wiring 5 Connect 2 wire data bus wiring 6 Connect iL...

Page 3: ...nd discard before field wiring This includes cardboard spacers in small cabinets and plastic tie wraps used on all SCMR relay modules SCMR Branch Circuit OCP SCCR NOTE Cabinets containing SCMR modules...

Page 4: ...ct operating conditions The cabinets do not contain fans Allowing airflow around the panel will enhance the reliability and longevity of all models Locating panels away from heat generating equipment...

Page 5: ...l cabinets have been designed to provide a clear layout and logical progression for all power circuits The main supply conductors enter at the top panel Input power is then fed to the modules inside t...

Page 6: ...on the interior DIN rail per the order specifications Each 0 10V dimmer requires a corresponding relay from the SCMR1220 NA to turn the lighting load ON OFF This mapping is performed during programmi...

Page 7: ...R1 RJ PC connection device A PC can be connected to the iLumin Plus panel using the SW2 cable kit plugging into the RJ port on the CR1 RJ If this iLumin Plus panel is connected to the lighting network...

Page 8: ...to access the lighting network via the buildign LAN or VLAN Note The EG2 can be use as a LAN bridge to connect different building lighting networks as a single lighting network over the building LAN...

Page 9: ...de taille La d sob issance aux instructions suivantes repr sente un risque de blessures y compris la mort et de dommages mat riels AVERTISSEMENT EXON RATION DE RESPONSABILIT Eaton n assume aucune resp...

Page 10: ...limentation du panneau 3 Raccordement du c blage de relais 4 Raccordement du c blage du gradateur de 0 10 V 5 Raccordement des deux c bles de conducteur du bus de donn es 6 Raccordement du c blage du...

Page 11: ...que REMARQUE SUR LA PROTECTION CONTRE LES SURINTENSIT S et LE COURANT DE COURT CIRCUIT NOMINAL du circuit r sonance coupl e magn tique Les armoires qui contiennent les modules r sonance coupl e magn t...

Page 12: ...armoires ne comportent pas de ventilateur Permettre une circulation d air autour du panneau am liorera la fiabilit et la dur e de vie de tous les mod les Installer les panneaux loin du mat riel qui g...

Page 13: ...et une progression logique pour tous les circuits d alimentation Les conducteurs de l alimentation principale p n trent dans le haut du panneau La puissance d entr e est ensuite aliment e vers les mo...

Page 14: ...Humidit entre 0 et 95 sans condensation Les modules de gradation SCMH1200 NA sont pr alablement mont s l int rieur du rail DIN conform ment aux sp cifications de la commande Chaque gradateur de 0 10 V...

Page 15: ...ge Les moyens et les grands panneaux iLumin Plus comprennent le dispositifs de connexion pour ordinateur CR1 RJ Un ordinateur peut tre raccord au panneau iLumin Plus l aide de la trousse de c bles SW2...

Page 16: ...suite iCANsoft pour le processus de configuration Connexion Ethernet Wiring Information Connection RJ45 connector Use Category 5 or Category 6 cable minimum Connect Connect to building LAN or VLAN for...

Page 17: ...e estas instrucciones puede provocar lesiones graves incluida la muerte y da os a la propiedad ADVERTENCIA RENUNCIA DE RESPONSABILIDAD Eaton no asume ninguna responsabilidad por da os o p rdidas de ni...

Page 18: ...te el recinto 2 Conecte la alimentaci n del panel 3 Conecte el cableado del rel 4 Conecte el cableado del atenuador de 0 10V 5 Conecte el cableado del bus de datos de 2 cables 6 Conecte el cableado de...

Page 19: ...e separadores de cart n en peque os armarios y envolturas de pl stico que se usan en todos los m dulos SCMR rel s Circuito derivado SCMR OCP y SCCR NOTA Los armarios que contienen m dulos SCMR NO incl...

Page 20: ...miento correctas Los armarios no contienen ventiladores Permitir el flujo de aire alrededor del panel mejorar la confiabilidad y longevidad de todos los modelos La ubicaci n de paneles lejos de equipo...

Page 21: ...ise ados para proporcionar un dise o claro y una progresi n l gica para todos los circuitos de alimentaci n Los conductores principales de suministro ingresan en el panel superior La corriente de entr...

Page 22: ...n Los m dulos de atenuaci n SCMH1200 NA se premontar n en el riel DIN interior seg n las especificaciones del pedido Cada atenuador de 0 10V requiere un rel correspondiente del SCMR1220 NA para ENCEND...

Page 23: ...4 Conect ndose a la red de iluminaci n Los paneles iLumin Plus medianos y grandes incluyen el dispositivo de conexi n CR1 RJ PC Se puede conectar una PC al panel de iLumin Plus utilizando el kit de ca...

Page 24: ...Category 6 cable minimum Connect Connect to building LAN or VLAN for lighting network access Note The EG2 can be used to access the lighting network via the buildign LAN or VLAN Note The EG2 can be u...

Reviews: