April 2015
Diesel Plus Fire Pump Controllers
Fire Pump Controllers
1-3
Features
K. Where shutdown of the pump(s) due to low suc-
tion pressure is required, it shall be accom-
plished without the addition of a separate panel
or enclosure. The LCD display shall indicate low
suction shutdown. Resetting of the condition
shall be automatic or manual as selected by the
user.
L. Means shall be provided to test the operation of
all LED’s to ensure their functionality.
7.
Programming Menu
A. The programming menu shall have the ability to
enable an entry password.
B. The programming menu shall be limited to two
(2) levels of password protection.
C. The controller shall have three (3) languages as
a standard, English, French, and Spanish, with
the ability to add a fourth language.
D. The programming menu shall be grouped into 7
main menu headings as follows:
1. Regional Settings
2. Pressure Settings
3. Timer Values
4. Input/Output Menu
5. System Configuration (password protected)
6. Language
7. Main Menu Password
8.
Custom Inputs/Outputs
A. The controller shall come standard with nine (9)
custom inputs, two (2) programmable LED indi-
cators, and two (2) future outputs, with the ability
to add up to another 8 outputs via optional relay
boards.
B. The user shall be able to program the future in-
puts/outputs and optional relays through the
main programming menu.
C. The inputs shall be selectable based on the fol-
lowing criteria:
1. User selected message or twenty four (24)
predetermined messages.
2. Energize the common alarm relay when the
input is received.
3. Link to a future relay and/or LED indicator.
4. Alarm latched until reset.
5. Normally open or closed input.
6. On-delay timer.
7. Energize the buzzer when the input is re-
ceived.
D. The LED indicators shall be selectable based on
the following criteria:
Indication based on a minimum of fourteen (14)
predetermined alarms or a custom input.
E. The future relays shall be selectable based on
the following criteria:
1. Output based on a minimum of forty (40)
predetermined alarms, controller status or a
custom input.
2. Latched until reset.
3. Energized under normal conditions.
4. On or off delay timer on the output.
9.
Manufacturer
A. The controller shall be microprocessor based
as manufactured by Eaton Industries (Canada)
Co.
For more information visit:
www.chfire.com
PS081002EN