Diesel Plus Fire Pump Controllers
Fire Pump Controllers
1-2
Features
C. The controller shall have a 4 line by 40 character
LCD display mounted on a panel opening in the
front door. The LCD display shall indicate the fol-
lowing:
1. Main screen displaying system pressure,
Battery #1/#2 voltage and amperage, opera-
tion mode, shutdown mode, custom mes-
sages, alarms, timers, date, and time.
2. Set point review screen displaying the pro-
grammed pressure start and stop points, and
weekly test time.
3. Controller statistics screen, including:
a. Powered Time
b. Engine Run Time
c. Number of Cranks
d. Number of Starts
e. Last Engine Start Time
f.
Last Engine Run Time
g. Last Low Pressure Start
h. Minimum Battery #1 Voltage
i.
Maximum Battery #1 Voltage
j.
Minimum Battery #2 Voltage
k. Maximum Battery #2 Voltage
l.
Minimum Battery #1 Amps
m. Maximum Battery #1 Amps
n. Minimum Battery #2 Amps
o. Maximum Battery #2Amps
p. Minimum System Pressure
q. Maximum System Pressure
r.
Last System Startup
s. Last Engine Test
t.
Last Low Oil Pressure
u. Last Overspeed
v. Last Fail To Start
w. Last Low Fuel
x. Last Charger Failure
y. Last Battery Failure
z. Last ECM Alarm
4. Controller diagnostics screen, including:
a. Date & Time
b. Firmware Version
c. Shop Order Number
d. Customer Order Number
e. Battery Voltage
f.
Internal Board Voltage
g. Transformer Output Voltage
h. Current Transformer Outputs
i.
Pressure Transducer Calibrated
Settings
j.
Input Status
k. Relay Status
5. Display last messages screen that will dis-
play at least the last 10,000 alarms / mes-
sages stored in the controllers' memory.
6. Display up to ten (10) custom messages of
up to 100 characters each, which will contin-
ually scroll across the fourth line of the dis-
play.
7. Remaining time left on active timers.
D. The controller shall be supplied with six (6)
green status LED’s for the following:
1. Engine Run
2. Remote Start
3. Low Pressure
4. Interlock On
5. Deluge Valve
6. One Programmable LED
E. The controller shall be supplied with twenty (20)
red alarm LED’s to indicate the following:
1. BATTERY #1 FAILURE
2. BATTERY #2 FAILURE
3. CHARGER #1 FAILURE
4. CHARGER #2 FAILURE
5. SPEED SWITCH FAULT
6. ECM SELECTOR IN ALT POSITION
7. FUEL INJECTION MALFUNCTION
8. LOW SUCTION PRESSURE
9. FAIL TO START
10. HIGH ENGINE TEMP.
11. LOW OIL PRESSURE
12. ENGINE OVERSPEED
13. LOW FUEL
14. ECM WARNING
15. ECM FAILURE
16. HIGH RAW WATER TEMPERATURE
17. LOW ENGINE TEMPERATURE
18. LOW RAW WATER FLOW
19. FUEL SPILL
20. One Programmable LED
F. The microprocessor logic board shall be
available with:
1. A USB port for transference of message his-
tory, controller status, diagnostics,
configuration, statistics and the ability to up-
date firmware.
2. An optional Ethernet port for direct connec-
tion to a computer for data transfer.
3. An optional RS485 Serial port for communi-
cation to various external software programs.
4. An optional RS232 Serial Port
G. The controller shall come complete with an em-
bedded web page which allows viewing of the
controllers' current status, data values, pro-
grammed set points, and downloadable history.
H. A Fail-to-Start alarm shall occur if the engine
does not start after the crank cycle.
I.
A sequential start timer, weekly test timer and
AC Failure Start timer shall be provided as
standard.
J. The controller shall be supplied with interlock
and shutdown circuits as standard. A flashing
green LED shall indicate an interlock on condi-
tion.