INSTALLATION SPECIFICATION
Eaton Industries Pty Ltd
August 2010
10 Kent Road, Mascot, NSW 2020, Australia
Page
3
of
13
DOCUMENT# 510091
F
Fuse rating is less than or equal to the current rating of this unit.
F
TT models - Earth conductor uses either a suitably-rated cable or an armoured cable shield with
clamp for safety earth, and a separate, 16mm
2
or greater cable for the “Surge Return Earth”.
F
TN models - Earth conductor uses either a suitably-rated cable or an armoured cable shield with
clamp.
F
Load phase and neutral cables are connected to unit output only. Do not bypass neutral.
F
Input and output cables must be kept well apart. Minimum distance is 300mm.
F
IF INSTALLED IN A SWITCHBOARD, THE LOAD EARTH IS TO BE DIRECTLY CONNECTED
TO MAIN SYSTEM EARTH, NOT THIS UNIT.
F
Ensure that you have the appropriate termination fittings (lugs, clamps etc) as well as appropriate
tools for their installation. Installation of this unit requires all cables to be lugged.
F
Customer is prepared for supply disconnection to allow connection of this unit. Alternatively, install
the fuses and isolation switch at an appropriate time, allowing connection of this unit as required.
If everything appears OK, sign-off and proceed to the next stage. If you aren't sure about anything, or
have any questions, please contact Eaton or your distributor prior to commencing work.
Completed by:
Date: