SP2 Surge Protective Device

Installation & Operation

Instruction Manual

IB158003EN

Rev. 2

1.0 Introduction

This manual describes how to install a Surge 
Protective Device (SPD) in parallel (shunt) across the
AC supply of the following types of electrical 
systems:

•      Single-Phase

•      Split Phase

•      Three-Phase Wye

•      Three-Phase Delta

The SPD is designed to be installed on service 
entrance, branch panels, and/or individual 
equipment disconnects, and functions to protect
sensitive electronic equipment from damaging 
voltage transients. The connecting wires do not
carry supply current. Instead, they carry only 
short-duration currents that are associated with a
transient event.

These instructions do not cover all details, 
variations, or combinations of the equipment, its
storage, delivery, installation, checkout, safe 
operation, or maintenance. If you require further 
information regarding a particular application or 
installation that is not covered in this manual,
please contact Eaton’s Power Quality Technical Sup-
port at 1-800-809-2772, option 4, option 2.

1.1 Safety Precautions

A licensed/qualified electrician must complete all 
instructions described in this manual in accordance
with the U.S. National Electrical Code, state and
local codes, or other applicable country codes. All
electrical codes supersede these instructions.

Improper installation can cause death, injury
and/or equipment damage. Follow all warnings
and cautions. Completely read and understand the
information in this instruction manual before 
attempting to install or operate this equipment.

Improper wiring could cause death, injury, and/or
equipment damage. Only licensed/qualified 
electricians who are trained in the installation and
service of electrical devices are to install and service
this equipment.

Use appropriate safety precautions and 
equipment for arc flash protection.

During normal operation, hazardous voltages are 
present inside the SPD.

When servicing the SPD, follow all safe work
practices to avoid electrical shock.

Do not perform a high-pot test with the SPD 
connected to the electrical system. Failure to 
disconnect the SPD during a high-pot test will result
in damage to the SPD.

Do not install with lead length less than six (6)
inches.

1.2 Catalog Numbering System

Series

Voltage Code

SP2-

120 = 120V single-phase
240 = 240V single-phase
240S = 240V split-phase
240D = 240 delta
480D = 480 delta
208Y = 120/208 wye
480Y = 277/480 wye
600Y = 347/600 wye

4.0 Specifications

5.0 Warranty

Eaton warrants these products for a period of 2
years from the date of delivery to the purchaser to
be free from defects in both workmanship and 
materials. Eaton assumes no risk or liability for 
results of the use of the products purchased from it,
including but without limiting the generality of the
foregoing: (1) The use in combination with any 
electrical or electronic components, circuits, 
systems, assemblies, or any other materials or 
substances; (2) Unsuitability of any product for use
in any circuit or assembly. Purchaser’s rights under
the warranty shall consist solely of requiring Eaton
to repair, or at Eaton’s sole discretion, replace, free
of charge, F.O.B. factory, and defective items 
received at said factory within said term determined
by Eaton to be defective. The giving of or failure to
give any advice or recommendations by Eaton shall
not constitute any warranty by or impose any 
liability upon Eaton. 

The foregoing constitutes the sole and exclusive 
liability of Eaton AND IS IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESSED, IMPLIED OR
STATUTORY AS TO THE MERCHANTABILITY, 
FITNESS FOR PURPOSE SOLD, DESCRIPTION,
QUALITY, PRODUCTIVENESS OR ANY OTHER 
MATTER. In no event shall Eaton be liable for 
special or consequential damages or for delay in
performance of the warranty. This warranty does
not apply if the product has been misused, abused,
altered, tampered with, or used in applications other
than specified on the nameplate. At the end of the
warranty period, Eaton shall be under no further
warranty obligation expressed or implied. The 
product covered by this warranty certificate can
only be repaired or replaced by the factory. For help
on troubleshooting the SPD, or for warranty 
information, call 1-800- 809-2772, Option 4, 
sub-option 2. Repair or replacement units will be 
returned collect. If Eaton finds the return to be a
manufacturer’s defect, the product will be returned
prepaid.

Eaton
1000 Cherrington Parkway
Moon Township, PA 15108-44312, USA
www.eaton.com/spd
For Technical Support, please call 1-800-809-2772

© Eaton Corporation

All Right Reserved

Description

Ratings

Surge current capacity per phase (Imax)

45kA

Nominal Discharge Current (In) 

10kA

Short circuit current rating (SCCR)

200kA

SPD type 

Type 1 (can also be used in Type 2 applications)

System voltages available (VAC)

Single-Phase

120/240

Split-phase

240

Three-phase wye 

208, 480, 600

Three-phase delta

240, 480

Protection modes

Single-phase

L-N

Split-phase

L-N

Three-phase wye

L-G, L-L

Three-phase delta

L-G, L-L

Maximum continuous operating voltage (MCOV)

SP2-120

150V

SP2-240

320V

SP2-240S

150V

SP2-208Y

150V

SP2-480Y

320V

SP2-600Y

420V

SP2-240D

320V

SP2-480D

550V

Input power frequency

50/60Hz

Enclosure rating

NEMA 4X

Operating temperature

-40°C through 65°C (-40°F through 149°F)

Operating humidity

5% through 95%, noncondensing

Operating altitude

Up to 12,000 ft (3658m)

Agency certification and approvals

UL1449 3

rd

Edition Type 1 Listed device

Warranty

2 years