Installation
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
17
Step 3 - Install load circuit breakers (if required)
Ignore this task if the load circuit breakers are already fitted.
Select the required load circuit breakers from the following list (see position
restrictions in point 2):
Circuit breaker rating Maximum load current
6A
4.8A
10A 8A
15A 12A
20A 16A
25A 20A
30A 24A
See Spare Parts on page
for circuit breaker types and purchasing
information. The current rating of the circuit breakers must be derated to
80%.
1
Remove the circuit breaker cover.
2
Plug in the load circuit breakers according to following restrictions:
Top row (1-2):
6A, 10A or 15A only
Top row (3-5):
6A, 10A, 15A, or 20A only
Bottom row (6-7):
6A, 10A or 15A only
Bottom row (8-10):
any value (6-30A)
3
Fit circuit breaker blank covers in all unused positions.
4
Replace the circuit breaker cover.
5
Switch the circuit breakers to the OFF (O) position.