Maintenance
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
49
Step 2 - Remove circuit breaker cover
Step 3 - Pull out the circuit breaker
Any Fuse Fail alarm will clear.
Step 4 - Plug in new circuit breaker or replace cover
Either:
•
See instructions in following section for installing a new circuit breaker,
or
•
Fit a circuit breaker blank cover and replace the circuit breaker cover.
Procedure complete
Installing a Circuit Breaker
Step 1 - Disconnect the load or battery module(s) (if required)
•
If installing a load circuit breaker then switch off the equipment (if any)
connected to the circuit breaker.
Refer to the equipment supplier's instructions on switching off
equipment.
•
If installing a battery circuit breaker then unplug the battery module(s)
(if any) connected to the circuit breaker.
Step 2 - Remove circuit breaker cover
Step 3 - Plug in the circuit breaker
•
For a battery circuit breaker a
Battery Fuse Fail
alarm will occur at the
system controller.
•
For a load circuit breaker a
Load Fuse Fail
alarm will occur at the system
controller if equipment is connected to the circuit breaker.