Enterprise Power Solutions Installation and Operation Guide
16
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
Step 2 - Install battery circuit breaker(s) (if required)
Ignore this task if:
•
The battery circuit breakers are already fitted, or
•
No battery modules will be connected (see details on page
1
The EPS2/EPS5 has two battery connectors (with two battery circuits
per connector). Fit a battery circuit breaker for each battery connector to
be used.
for the battery circuit current rating.
See Spare Parts on page
for circuit breaker type and purchasing
information. The current rating of the circuit breakers must be derated to
80%.
2
Remove the circuit breaker cover.
3
Remove the battery circuit breaker blank cover in position 1 and plug in
the battery circuit breaker.
4
If required, repeat for position 2 or fit the circuit breaker blank cover.
5
Switch the circuit breaker(s) to the OFF (O) position.
"
Circuit breaker cover
#
Battery circuit breaker (1of 2 shown)
$
Circuit breaker blank cover (to cover
unused circuit breaker position 2 if
required)