6. Function blocks
6.2 Interrupt function blocks
If an output is defined as a physical output on base device in the parameters for the
interrupt program, the output will be assigned an identifier of QP01 – QP04 and will act
directly on device output Q1 – Q4.
Zur Verarbeitung des Interrupt-Programmes hat der Funktionsbaustein einen eigenen
Merkerbereich von 32 Merker-Bits.
Available functions within an interrupt program
Interrupt programs are not available when using the EDP programming language.
Action
KOP
FBS
ST
New network
√
√
√
Input/output inverter
√
√
√
Contacts
Make, Break, Constant 1, Constant 0
Coils
Contactor, Negated contactor, Set, Reset
Jump functions
Jump if 1, Jump if 0, Return if 1, Return if 0
Logic gates
AND, AND NOT, OR, OR NOT, XOR, XNOR
Conditional statement
–
–
√
Simple alternative
–
–
√
Multiple alternatives
–
–
√
6.2.1.3 The function block and its parameters
Function block inputs
Description
Note
(Bit)
EN
1: Activates the function block.
The checkbox for the
Function block release by EN is neces-
sary
parameter must first be enabled
RE
1: Sets the actual counter value to zero
I1
The states of the bit inputs from the main pro-
gram will be provided to the interrupt program
I2
I3
I4
(DWord)
SV
Setpoint
Integer value range:
-2,147,483,648 to +2,147,483,647
Assigning operands
You can assign the following operands to the function block inputs that are numeric
inputs.
Operands
Value inputs
Constant, timer constant
x
MD, MW, MB - Markers
x
NB, NW, ND - NET markers
x
nNB, nND, nND- NET markers
x
easyE4
11/18 MN050009 EN www.eaton.com
407
Summary of Contents for easyE4 series
Page 1: ...Manual 11 18 MN050009 EN easyE4 Manual...
Page 4: ......
Page 16: ...12 easyE4 11 18 MN050009 EN www eaton com...
Page 22: ...0 1 About this manual 18 easyE4 11 18 MN050009 EN www eaton com...
Page 169: ...easyE4 11 18 MN050009 EN www eaton com 165...
Page 490: ...7 System settings 7 16 Time and Date setting 486 easyE4 11 18 MN050009 EN www eaton com...
Page 520: ...9 easyE4 inside 9 7 NET network 516 easyE4 11 18 MN050009 EN www eaton com...
Page 570: ...11 Connection to other devices 11 6 E mail function 566 easyE4 11 18 MN050009 EN www eaton com...
Page 578: ...12 Faults 12 4 Functionality of the NET faulty 574 easyE4 11 18 MN050009 EN www eaton com...
Page 582: ...13 Maintenance 13 3 Storage transport and disposal 578 easyE4 11 18 MN050009 EN www eaton com...
Page 594: ...590 easyE4 11 18 MN050009 EN www eaton com...