9. easyE4 inside
9.4 Time behavior of the inputs and outputs
9.4.1.2 Delay time with DEBOUNCE deactivated
When DEBOUNCE is deactivated, the typical delay time for DC signals on the input for
easyE4 base devices caused by the hardware lies between 0.025 ms and 0.25 ms (A).
Figure 240: Switching behavior with DEBOUNCE deactivated
Typical delay times with DEBOUNCE deactivated are:
l
On-delay for:
l
I1 to I4 easyE4 default: 0.025 ms
l
I1 to I4 EASY806-DC-SWD: 0.02 ms
l
I5 to I12: 0.25 ms
l
Off delay for:
l
I1 to I4 easyE4 default: 0.025 ms
l
I1 to I4: 0.02 ms
l
I5, to I8: 0.4 ms
When using high-speed counter function blocks, the delay time
for the input signals must not exceed 0.025 ms. DEBOUNCE
must therefore be deactivated.
When DEBOUNCE is deactivated ensure that input signals are
free of noise. The easyE4 device responds to very short sig-
nals.
To allow reliable recognition and processing of the input signal,
it must be applied stably for a certain duration, the length of
which depends on the circuit diagram processing cycle time.
508
easyE4
11/18 MN050009 EN www.eaton.com
Summary of Contents for easyE4 series
Page 1: ...Manual 11 18 MN050009 EN easyE4 Manual...
Page 4: ......
Page 16: ...12 easyE4 11 18 MN050009 EN www eaton com...
Page 22: ...0 1 About this manual 18 easyE4 11 18 MN050009 EN www eaton com...
Page 169: ...easyE4 11 18 MN050009 EN www eaton com 165...
Page 490: ...7 System settings 7 16 Time and Date setting 486 easyE4 11 18 MN050009 EN www eaton com...
Page 520: ...9 easyE4 inside 9 7 NET network 516 easyE4 11 18 MN050009 EN www eaton com...
Page 570: ...11 Connection to other devices 11 6 E mail function 566 easyE4 11 18 MN050009 EN www eaton com...
Page 578: ...12 Faults 12 4 Functionality of the NET faulty 574 easyE4 11 18 MN050009 EN www eaton com...
Page 582: ...13 Maintenance 13 3 Storage transport and disposal 578 easyE4 11 18 MN050009 EN www eaton com...
Page 594: ...590 easyE4 11 18 MN050009 EN www eaton com...