12
XSTORAGE HOME POWER METERS MANUAL
MN700001EN March 2019 www.eaton.com/xstorage
The Eastron SDM120CT belongs to the 120 power meter
series. The power meter works in combination with the current
transformer (CT) as it is shown in the picture below. The current
transformer is Eastron that belongs to the ESCT-TU16 series.
Figure 22: Eastron SDM120CT and current transformer
(CT) product overview
The dimensions [mm] of the meter are as shown below:
Figure 23: Eastron SDM120CT
The DIN rail mount construction enables the power meter to
be installed in a compact electrical distribution box (Figure 24).
Figure 24: DIN Rail mount for Eastron meter
During the installation of the power meter, no additional
protective devices are required. The meter connection
terminals must be directly connected to the L (line) and N
(neutral) wires. The split core CT is installed on the L phase
in the same direction as the current (see Figure 25). After the
CT is wired to the S1 and S2 terminals of the power meter,
it is supplied directly by L (phase) and N (neutral) that are
respectively wired to the terminal 3 and 4 of the power meter
itself as it is displayed in the Figure 25.
5. Eastron SDM120CT: Technical
specifications, installation and wiring
Figure 25: How to wire the current transformer and the
power meter to the L and N