background image

is overcurrent protection, which is achieved by analyzing 
the current signals received from the circuit breaker current 
sensors and initiating trip signals to the circuit breaker trip 
actuator when pre-determined current levels and time delay 
settings are exceeded.

The protection section of the Digitrip RMS Trip Unit can 
be equipped with up to five phase and two ground fault 
time current adjustments. The short delay and ground fault 
pick-up adjustments can be arranged for either a flat or I

2

response. The exact selection of the available adjustments 
must be chosen to satisfy the protection needs of the spe-
cific installation.

LEDs provide mode of trip indication for ground fault, over-
load and short circuit trip operations.

Digitrip RMS Trip Unit types LS and LSG are not equipped 
with an adjustable instantaneous trip element, but are 
provided with a making current release (discriminator). A 
high-level instantaneous override circuit is provided to insure 
rapid circuit clearing under abnormal fault current conditions.

Digitrip RMS Trip Units are available in four basic models, 
the Digitrip RMS 510, 610, 810 and 910 (Figure 2a). Sepa-
rate instruction leaflets referenced in Section 8.1 cover the 
features and functions of each model. This instruction book 
is arranged to describe the unique features of each type as 
applied in Types DSII and DSLII Low-Voltage AC Power Cir-
cuit Breakers. Table 1 presents the available characteristics 
of each of the four trip unit models.

The Digitrip OPTIM Trip Unit System utilizes two basic trip 
unit models with the Type DSII Low Voltage AC Power Circuit 
Breaker, the OPTIM 750 and OPTIM 1050 Trip Units (Figure 
2b). The featured parts of a Digitrip OPTIM Trip Unit System 
are:

1.  OPTIM 750 or 1050 RMS sensing trip units
2. OPTIMizer Hand Held Programmer
3. Breaker Interface Module

The OPTIMizer Hand Held Programmer plugs into the front 
of OPTIM 750 or 1050 Trip Units to access, display and con-
figure trip unit information, and establish trip unit addresses. 
The panel mounted  Breaker Interface Module provides all 
the same features and capabilities as the OPTIMizer Hand 
Held Programmer, plus energy monitoring, local/remote indi-
cation, and communications capabilities, except that only the 
Hand Held Programmer can establish trip unit addresses. 
Separate instruction manuals, referenced in Section 8.3, 
cover all the details associated with the OPTIMizer Hand 
Held Programmer and the Breaker Interface Module.

The following circuit breaker accessories are available to pro-
vide supplementary protection, signaling and test functions:  
(Refer to Section 3.10 of I.B. 694C694 for details)

1.  Undervoltage Trip Device
2. Portable Test Kit - See CAUTION on page 4.
3. Latch Check Switch
4. Auxiliary Switches
5. Overcurrent Trip Switch

3.0  Ratings Plugs

Rating Plugs, as shown in Figure 3, determine the continu-
ous current rating of the circuit breaker. All protection func-
tion settings on the face of the trip unit for the Digitrip RMS 
510, 610, 810 and 910 are expressed in per unit multiples 
of the plug rating (I

n

) or the long delay current setting (I

r

). 

The Digitrip OPTIM 750 and 1050 use the same rating plug 
family as Digitrip RMS. The plug rating (I

n

) determines the 

maximum continuous current rating of the circuit breaker. All 
the protection function pickup settings are based on the plug 
rating (I

n

). These pickup settings are ultimately loaded into 

the trip unit in per unit, but are displayed as an ampere value 
for ease of use by the user.

Available rating plugs are shown in Table 2. Plugs are suitable 
for 50 or 60Hz operation, but must be selected to match the 
desired continuous current rating of the circuit breaker as 
well as the installed sensor rating.

Rating plugs are equipped with a back-up battery, as shown 
in Figure 3, to maintain the trip indication following a circuit 
breaker tripping operation when external control power is 
not available. The battery is a long-life lithium type that is 
replaceable from the front of the trip unit without remov-
ing the rating plug. Replacement types and instructions are 
provided in the Digitrip RMS Trip Unit instruction leaflets 
referred to in Section 8.1.

Following a trip operation and with no supplementary control 
power available, the battery would maintain the mode of trip 
LED for approximately 60 hours.

Effective July 2010

 

Instructional Leaflet

 IL8700C39-04

3

eaTOn CORPORaTIOn

 www.eaton.com

Summary of Contents for Digitrip RMS Series

Page 1: ...Potential Transformer Module 15 6 0 Testing 15 6 1 Functional Field Testing 15 6 1 1 Secondary Injection Testing 15 6 2 Performance Testing for Ground Fault Trip Units 18 6 2 1 Code Requirements 18 6...

Page 2: ...ing every application or circumstance which may arise If any questions arise contact Eaton for further information or instructions 1 0 Supplementary Information The instructions contained in this book...

Page 3: ...ies as the OPTIMizer Hand Held Programmer plus energy monitoring local remote indi cation and communications capabilities except that only the Hand Held Programmer can establish trip unit addresses Se...

Page 4: ...Effective July 2010 Instructional Leaflet IL8700C39 04 Figure 2a Typical Digitrip RMSTrip Unit Display Panels Figure 2b Typical Digitrip OPTIMTrip Unit Display Panels 4 eaton corporation www eaton com...

Page 5: ...ted using secondary currents provided by an Amptector Trip Unit test kit as illustrated in I L 33 791 Detailed instructions for testing trip units are given in the individual trip unit instruction lea...

Page 6: ...test receptacles for external field testing mounted in the breaker Figures 4 and 5 4 2 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit described in I L 29...

Page 7: ...gnal Contact High Load Alarm X X X X X Long Delay Trip X X X X X Short Circuit Trip X X X X X Ground Fault Trip o o o o o Ground Alarm Integral Test Provisions X X X X Trip Unit Status Indication LED...

Page 8: ...l Ground Fault GNDT l o l o Long Delay LDT l l Overtemperature TEMP l l External Trip EXTT l l Long Time Delay Pickup LDPU l l Over Range Trip ORNG l l Information Normal NORM l l Protection Settings...

Page 9: ...ting a Potential Transformer Module and a Power Relay Module mounted as shown in Figures 4 and 5 The Digitrip RMS 810 Trip Unit performs all the functions of the Digitrip RMS 610 Trip Unit with the ad...

Page 10: ...ze a fixed interchangeable rating plug to establish the continuous trip rating of the circuit breaker Rating plugs are interlocked to prevent use between different circuit breaker types Precise system...

Page 11: ...6 for OPTIM 750 In addition OPTIM 1050 Trip Units are capable of pro viding data on power quality and permit energy monitoring Energy Monitoring 1 Peak demand kW 2 Present demand kW 3 Forward energy...

Page 12: ...power required 5 2 Digitrip Trip Assembly The basic Digitrip Trip Assembly as shown in Figures 4 and 5 includes the following which could vary slightly depending upon the exact model of the Digitrip T...

Page 13: ...l sensing scheme which vectorially sums the outputs of the individual phase current sensors As long as the vecto rial sum is zero then no ground fault exists If the system neutral is grounded and a ne...

Page 14: ...t signal will be equivalent to a single BYZ sensor The BYZ current sensor styles shown in Figure 7 are avail able for all previously mentioned applications When either style sensor is used the ground...

Page 15: ...FORMER MODULE DISCONNECT PLUG IS CONNECTED DEATH OR SEVERE PERSONAL INJURY MAY RESULT AND THE POTENTIAL TRANSFORMER MODULE AND TRIP UNIT WILL BE DAMAGED REMOVE THE PTM DISCONNECT PLUG PRIOR TO PERFORM...

Page 16: ...AMPTECTORTEST KIT STYLES 140D481G02R 140D481G02RR OR 140D481G03 IN CONJUNCTION WITH A DIGITRIP ADAPTER STYLE 8779C02G01 SHOULD BE USED UNMODIFIED AMPTECTORTEST KIT STYLES 140D481G01 AND 140D481G02 SH...

Page 17: ...harge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Results Breaker Number Figure 9 Typical PerformanceTest Record Form Effe...

Page 18: ...ource apply a test current of 125 of the Digitrip Ground Fault Trip Unit pickup setting through one phase of the circuit breaker as shown in Figure 8a This should cause the breaker to trip in less tha...

Page 19: ...Curves for Types DSII and DSLII Circuit Breakers with Digitrip OPTIM 750 and 1050 Trip Units SC 6275 95 Typical Long Delay I2 t Short Delay I2 t Types DSII and DSLII rated up to 1200A SC 6276 95 Typic...

Page 20: ...______ By____________________________ Figure 10 TypicalTrip Function Record Digitrip Automatic trip operation record Circuit No Address Breaker Shop Order References ________________ _________________...

Page 21: ...Effective July 2010 Instructional Leaflet IL8700C39 04 21 eaton corporation www eaton com...

Page 22: ...Effective July 2010 Instructional Leaflet IL8700C39 04 22 eaton corporation www eaton com...

Page 23: ...Effective July 2010 Instructional Leaflet IL8700C39 04 23 eaton corporation www eaton com...

Page 24: ...icies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR...

Reviews: