background image

TESTING OF A CIRCUIT BREAKER SHOULD BE DONE 
ONLY IN THE “TEST,” “DISCONNECTED” OR “REMOVE” 
CELL POSITIONS.

6.2  Performance Testing for Ground 
Fault Trip Units

6.2.1  Code Requirements

The National Electrical Code under Article 230-95-C requires 
that any ground fault protection system be performance 
tested when first installed. The test shall be conducted in 
accordance with approved instructions provided with the 
equipment. A written record of this test shall be made and 
shall be available to the authority having inspection jurisdic-
tion.

6.2.2  Standards Requirements

As a follow-up to the basic performance requirements stipu-
lated by the N.E.C. in Section 6.2.1, UL Standards No. 1053 
requires that certain minimum instructions must accompany 
each ground fault protection system. The following article 
plus the test record form illustrated in Figure 9 are intended 
to satisfy this requirement.

6.2.3  General Test Instructions

The interconnected system shall be evaluated in accordance 
with the equipment assembler’s detailed instructions by 
qualified personnel.

The polarity of the neutral sensor connections, if used, must 
agree with the equipment assembler’s detailed instructions 
to avoid improper operations following apparently correct 
simulated test operations. Where a question exists, consult 
the specifying engineer and/or equipment assembler.

The grounding points of the system shall be verified to 
determine that ground paths do not exist that would bypass 
the sensors. The use of high voltage testers and resistance 
bridges may be used.

 warNINg

THERE IS A HAZARD OF ELECTRICAL SHOCK OR BURN 
WHENEVER WORKING IN OR AROUND ELECTRICAL 
EQUIPMENT. ALWAYS TURN OFF POWER SUPPLYING 
THE BREAKER BEFORE CONDUCTING TESTS.

Effective July 2010

 

Instructional Leaflet

 IL8700C39-04

Using a low voltage, 0-24 volts, high current, AC source, 
apply a test current of 125% of the Digitrip Ground Fault Trip 
Unit pickup setting through one phase of the circuit breaker, 
as shown in Figure 8a. This should cause the breaker to trip 
in less than 1 second, and an alarm indicator should operate, 
if one is supplied. Reset the breaker and the alarm indicator. 
Repeat the test on the other two phases.

If the system is a 4-wire system with a neutral current sen-
sor, apply the same current as described above through one 
phase of the breaker, returning through the neutral sensor, 
as shown in Figure 8b. The breaker should not trip, and the 
alarm indicator, if supplied, should not operate. Repeat the 
test on the other two phases. 

If the system is a 3-wire system with no neutral current 
sensor, apply the same current as described above through 
any two phases of the breaker, with the connections exactly 
as shown in Figure 8c. The breaker should not trip, and the 
alarm indicator, if supplied, should not operate. Repeat the 
test using the other two combinations of breaker phases.

 CauTION

FIELD TESTING SHOULD BE USED FOR FUNCTIONAL 
TESTING AND NOT FIELD CALIBRATION OF THE DIGI-
TRIP GROUND FAULT TRIP UNIT.

ANY TEMPORARY CONNECTION MADE FOR THE PUR-
POSE OF CONDUCTING TESTS SHOULD BE RESTORED 
TO PROPER OPERATING CONDITIONS BEFORE RE-
TURNING THE BREAKER TO SERVICE.

THE RESULTS OF THE TEST ARE TO BE RECORDED ON 
THE TEST FORM PROVIDED (FIGURE 9).

7.0  Record Keeping

For convenience, a trip function record as shown in Figure 10 
is included. This record should be filled in giving the indicat-
ed reference information and initial time/current trip function 
settings. If desirable, a copy could be made and attached to 
the interior of the breaker cell door or other visible location. 
Figure 11 is also included as a convenient way of providing a 
place for recording test data and actual trip values. 

Ideally, sheets of this type should be used and maintained 
by those personnel in the user’s organization that have the 
responsibility for protection equipment.

18

eaTOn CORPORaTIOn

 www.eaton.com

Summary of Contents for Digitrip RMS Series

Page 1: ...Potential Transformer Module 15 6 0 Testing 15 6 1 Functional Field Testing 15 6 1 1 Secondary Injection Testing 15 6 2 Performance Testing for Ground Fault Trip Units 18 6 2 1 Code Requirements 18 6...

Page 2: ...ing every application or circumstance which may arise If any questions arise contact Eaton for further information or instructions 1 0 Supplementary Information The instructions contained in this book...

Page 3: ...ies as the OPTIMizer Hand Held Programmer plus energy monitoring local remote indi cation and communications capabilities except that only the Hand Held Programmer can establish trip unit addresses Se...

Page 4: ...Effective July 2010 Instructional Leaflet IL8700C39 04 Figure 2a Typical Digitrip RMSTrip Unit Display Panels Figure 2b Typical Digitrip OPTIMTrip Unit Display Panels 4 eaton corporation www eaton com...

Page 5: ...ted using secondary currents provided by an Amptector Trip Unit test kit as illustrated in I L 33 791 Detailed instructions for testing trip units are given in the individual trip unit instruction lea...

Page 6: ...test receptacles for external field testing mounted in the breaker Figures 4 and 5 4 2 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit described in I L 29...

Page 7: ...gnal Contact High Load Alarm X X X X X Long Delay Trip X X X X X Short Circuit Trip X X X X X Ground Fault Trip o o o o o Ground Alarm Integral Test Provisions X X X X Trip Unit Status Indication LED...

Page 8: ...l Ground Fault GNDT l o l o Long Delay LDT l l Overtemperature TEMP l l External Trip EXTT l l Long Time Delay Pickup LDPU l l Over Range Trip ORNG l l Information Normal NORM l l Protection Settings...

Page 9: ...ting a Potential Transformer Module and a Power Relay Module mounted as shown in Figures 4 and 5 The Digitrip RMS 810 Trip Unit performs all the functions of the Digitrip RMS 610 Trip Unit with the ad...

Page 10: ...ze a fixed interchangeable rating plug to establish the continuous trip rating of the circuit breaker Rating plugs are interlocked to prevent use between different circuit breaker types Precise system...

Page 11: ...6 for OPTIM 750 In addition OPTIM 1050 Trip Units are capable of pro viding data on power quality and permit energy monitoring Energy Monitoring 1 Peak demand kW 2 Present demand kW 3 Forward energy...

Page 12: ...power required 5 2 Digitrip Trip Assembly The basic Digitrip Trip Assembly as shown in Figures 4 and 5 includes the following which could vary slightly depending upon the exact model of the Digitrip T...

Page 13: ...l sensing scheme which vectorially sums the outputs of the individual phase current sensors As long as the vecto rial sum is zero then no ground fault exists If the system neutral is grounded and a ne...

Page 14: ...t signal will be equivalent to a single BYZ sensor The BYZ current sensor styles shown in Figure 7 are avail able for all previously mentioned applications When either style sensor is used the ground...

Page 15: ...FORMER MODULE DISCONNECT PLUG IS CONNECTED DEATH OR SEVERE PERSONAL INJURY MAY RESULT AND THE POTENTIAL TRANSFORMER MODULE AND TRIP UNIT WILL BE DAMAGED REMOVE THE PTM DISCONNECT PLUG PRIOR TO PERFORM...

Page 16: ...AMPTECTORTEST KIT STYLES 140D481G02R 140D481G02RR OR 140D481G03 IN CONJUNCTION WITH A DIGITRIP ADAPTER STYLE 8779C02G01 SHOULD BE USED UNMODIFIED AMPTECTORTEST KIT STYLES 140D481G01 AND 140D481G02 SH...

Page 17: ...harge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Results Breaker Number Figure 9 Typical PerformanceTest Record Form Effe...

Page 18: ...ource apply a test current of 125 of the Digitrip Ground Fault Trip Unit pickup setting through one phase of the circuit breaker as shown in Figure 8a This should cause the breaker to trip in less tha...

Page 19: ...Curves for Types DSII and DSLII Circuit Breakers with Digitrip OPTIM 750 and 1050 Trip Units SC 6275 95 Typical Long Delay I2 t Short Delay I2 t Types DSII and DSLII rated up to 1200A SC 6276 95 Typic...

Page 20: ...______ By____________________________ Figure 10 TypicalTrip Function Record Digitrip Automatic trip operation record Circuit No Address Breaker Shop Order References ________________ _________________...

Page 21: ...Effective July 2010 Instructional Leaflet IL8700C39 04 21 eaton corporation www eaton com...

Page 22: ...Effective July 2010 Instructional Leaflet IL8700C39 04 22 eaton corporation www eaton com...

Page 23: ...Effective July 2010 Instructional Leaflet IL8700C39 04 23 eaton corporation www eaton com...

Page 24: ...icies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR...

Reviews: