background image

Table 2. In general, plug ratings are available down through 
50% of the current sensor rating. 

The selection of available current sensors and rating plugs 
coupled with the wide range of long-delay current pick-up 
settings available on the Digitrip Trip Unit makes one set of 
sensors suitable for a number of current ratings. The Digitrip 
Trip Unit protection function settings are standard, and are 
usable with standard sensors of any rating, up to the frame 
rating of the circuit breaker. 
If sensors are changed because of changing load conditions, 
etc., it is only necessary to replace the rating plug and read-
just the Digitrip Trip Unit protection function settings to the 
new desired values. 

To insure the non-tampering of selected protection settings, 
a sealable plexiglass cover as shown in Figure 1 is provided. 
The cover is held in place by four cover screws. The non-tam-
pering feature is insured by the insertion of a standard meter 
seal through the holes in two of the cover retention screws. 

5.6  Potential Transformer Module

The Potential Transformer Module (PTM) is supplied with 
the Digitrip RMS 810, 910 and OPTIM 1050 Trip Units. It is 
mounted on the side of the Trip Assembly as shown in Fig-
ures 4 and 5. The PTM’s primary is connected to the circuit 
breaker’s bottom end conductors. This module provides volt-
age for computing the energy monitoring parameters.

The PTM disconnect plug is mounted above the PTM as 
shown in Figure 4. This plug must be disconnected prior to 
any dielectric testing of the circuit breaker.

 warNINg

DO NOT aTTEmpT TO pErfOrm DIElECTrIC (Or hIgh pOT Or 
hIgh VOlTagE) wIThsTaND TEsTs ON ThE CIrCuIT BrEakEr 
whIlE ThE pOTENTIal TraNsfOrmEr mODulE DIsCONNECT 
plug Is CONNECTED. DEaTh Or sEVErE pErsONal INJury may 
rEsulT aND ThE pOTENTIal TraNsfOrmEr mODulE aND TrIp 
uNIT wIll BE DamagED.

rEmOVE ThE pTm DIsCONNECT plug prIOr TO pErfOrmINg 
aNy DIElECTrIC (Or hIgh pOT Or hIgh VOlTagE) wIThsTaND 
TEsTs. rEplaCE ThE plug afTEr all TEsTINg Is COmplETED 
aND prIOr TO ClOsINg ThE BrEakEr as pEr ThE EsTaBlIshED 
OpEraTINg prOCEDurEs.

6.0  Testing

6.1  Functional Field Testing

A functional local test of a major portion of the Digitrip’s 
electronic circuitry and breaker’s mechanical trip assembly 
can be verified using the trip unit’s test receptacle. The test-
ing can verify the desired trip settings by performing Long 
Delay, Short Delay and Ground Fault functional tests. The 
Digitrip model and its associated Test Kit/Auxiliary Power 
Module requirements are listed in Table 5.

6.1.1  Secondary Injection Testing

The circuit breaker has a field test kit receptacle that can be 
used for secondary injection testing to test Digitrip RMS or 
Digitrip OPTIM Trip Units (Figure 4). With the Auxiliary Power 
Module installed, the circuit breaker can be tested using sec-
ondary currents provided by an Amptector Trip Unit test kit 
as illustrated in I.L. 33-791. Detailed instructions for testing 
trip units are given in the individual trip unit instruction manu-
als referenced in Section 8.1.

Table 5  Digitrip Functional Testing Hardware

 

Digitrip Model 

Testing Hardware

  Digitrip RMS 510, 610,  

Test Kit

  810 and 910 

(Style No. 140D481G03)

   

Test Kit Adapter

   

(Style No. 8779C02G01)

   

Auxiliary Power Module 

   

(Catalog No. PRTAAPM)

  Digitrip OPTIM 

OPTIMizer Hand Held Programmer

   

(Catalog No. OPTIMIZER)

   

Breaker Interface Module

   

(Catalog No. BIM)

   

Test Kit

   

(Style No. 140D481G03)

   

Test Kit Adapter

   

(Style No. 8779C02G01)

   

Auxiliary Power Module

   

(Catalog No. PRTAAMP)   

Effective July 2010

 

Instructional Leaflet

 IL8700C39-04

15

eaTOn CORPORaTIOn

 www.eaton.com

Summary of Contents for Digitrip RMS Series

Page 1: ...Potential Transformer Module 15 6 0 Testing 15 6 1 Functional Field Testing 15 6 1 1 Secondary Injection Testing 15 6 2 Performance Testing for Ground Fault Trip Units 18 6 2 1 Code Requirements 18 6...

Page 2: ...ing every application or circumstance which may arise If any questions arise contact Eaton for further information or instructions 1 0 Supplementary Information The instructions contained in this book...

Page 3: ...ies as the OPTIMizer Hand Held Programmer plus energy monitoring local remote indi cation and communications capabilities except that only the Hand Held Programmer can establish trip unit addresses Se...

Page 4: ...Effective July 2010 Instructional Leaflet IL8700C39 04 Figure 2a Typical Digitrip RMSTrip Unit Display Panels Figure 2b Typical Digitrip OPTIMTrip Unit Display Panels 4 eaton corporation www eaton com...

Page 5: ...ted using secondary currents provided by an Amptector Trip Unit test kit as illustrated in I L 33 791 Detailed instructions for testing trip units are given in the individual trip unit instruction lea...

Page 6: ...test receptacles for external field testing mounted in the breaker Figures 4 and 5 4 2 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit described in I L 29...

Page 7: ...gnal Contact High Load Alarm X X X X X Long Delay Trip X X X X X Short Circuit Trip X X X X X Ground Fault Trip o o o o o Ground Alarm Integral Test Provisions X X X X Trip Unit Status Indication LED...

Page 8: ...l Ground Fault GNDT l o l o Long Delay LDT l l Overtemperature TEMP l l External Trip EXTT l l Long Time Delay Pickup LDPU l l Over Range Trip ORNG l l Information Normal NORM l l Protection Settings...

Page 9: ...ting a Potential Transformer Module and a Power Relay Module mounted as shown in Figures 4 and 5 The Digitrip RMS 810 Trip Unit performs all the functions of the Digitrip RMS 610 Trip Unit with the ad...

Page 10: ...ze a fixed interchangeable rating plug to establish the continuous trip rating of the circuit breaker Rating plugs are interlocked to prevent use between different circuit breaker types Precise system...

Page 11: ...6 for OPTIM 750 In addition OPTIM 1050 Trip Units are capable of pro viding data on power quality and permit energy monitoring Energy Monitoring 1 Peak demand kW 2 Present demand kW 3 Forward energy...

Page 12: ...power required 5 2 Digitrip Trip Assembly The basic Digitrip Trip Assembly as shown in Figures 4 and 5 includes the following which could vary slightly depending upon the exact model of the Digitrip T...

Page 13: ...l sensing scheme which vectorially sums the outputs of the individual phase current sensors As long as the vecto rial sum is zero then no ground fault exists If the system neutral is grounded and a ne...

Page 14: ...t signal will be equivalent to a single BYZ sensor The BYZ current sensor styles shown in Figure 7 are avail able for all previously mentioned applications When either style sensor is used the ground...

Page 15: ...FORMER MODULE DISCONNECT PLUG IS CONNECTED DEATH OR SEVERE PERSONAL INJURY MAY RESULT AND THE POTENTIAL TRANSFORMER MODULE AND TRIP UNIT WILL BE DAMAGED REMOVE THE PTM DISCONNECT PLUG PRIOR TO PERFORM...

Page 16: ...AMPTECTORTEST KIT STYLES 140D481G02R 140D481G02RR OR 140D481G03 IN CONJUNCTION WITH A DIGITRIP ADAPTER STYLE 8779C02G01 SHOULD BE USED UNMODIFIED AMPTECTORTEST KIT STYLES 140D481G01 AND 140D481G02 SH...

Page 17: ...harge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Results Breaker Number Figure 9 Typical PerformanceTest Record Form Effe...

Page 18: ...ource apply a test current of 125 of the Digitrip Ground Fault Trip Unit pickup setting through one phase of the circuit breaker as shown in Figure 8a This should cause the breaker to trip in less tha...

Page 19: ...Curves for Types DSII and DSLII Circuit Breakers with Digitrip OPTIM 750 and 1050 Trip Units SC 6275 95 Typical Long Delay I2 t Short Delay I2 t Types DSII and DSLII rated up to 1200A SC 6276 95 Typic...

Page 20: ...______ By____________________________ Figure 10 TypicalTrip Function Record Digitrip Automatic trip operation record Circuit No Address Breaker Shop Order References ________________ _________________...

Page 21: ...Effective July 2010 Instructional Leaflet IL8700C39 04 21 eaton corporation www eaton com...

Page 22: ...Effective July 2010 Instructional Leaflet IL8700C39 04 22 eaton corporation www eaton com...

Page 23: ...Effective July 2010 Instructional Leaflet IL8700C39 04 23 eaton corporation www eaton com...

Page 24: ...icies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR...

Reviews: