background image

4.4  Digitrip RMS 910

The Digitrip RMS 910 Trip Assembly is similar to the Digitrip 
RMS 810. It is a communicating trip unit that provides all 
the functions described in Section 4.3 plus the addition of 
the following locally displayed and remotely communicated 
features: 

1. Phase to Phase Voltages Vab, Vbc, Vca
2. System Power Factor (PF)
3. Total Harmonic Distortion (THD) for Ia, Ib, Ic

The THD calculation also includes the individual harmonic 
currents up to the 27th harmonic as a percentage of the 
fundamental. Also included with the THD are provisions for 
waveform capture information via a host computer. Detailed 
information is provided in I.L. 29-889.

4.5  Digitrip OPTIM Model Consider-
ations

Trip unit testing is carried out by using the OPTIMizer Hand 
Held Programmer, the Breaker Interface Module, or a 
remote computer to select values of test current within a 
range of available settings. Basic protection functions are 
not affected during test operations. The testing capability is 
not intended for live primary current interruption. Two types 
of tests are possible, the “No Trip” and the “Trip” tests. 
Testing is not permitted to proceed if there is greater than 
0.4 per unit of current flowing on a phase circuit or 0.2 per 
unit of current on a ground circuit. The maximum permitted 
current value can be determined by multiplying the appro-
priate per unit value (0.4 or 0.2) times the ampere rating of 
the installed rating plug. An auxiliary power module (Cat. 
No. PRTAAPM) can be used to bench test a trip unit when 
the auxiliary power module is connected to a 120V 50/60Hz 
supply.

 CauTION

“TrIp” TEsTINg Of a CIrCuIT BrEakEr IN ThE CEll “CON-
NECTED” pOsITION Is NOT rECOmmENDED. ThE TrIppINg 
OpEraTION Of ThE CIrCuIT BrEakEr wIll CausE sErVICE DIs-
rupTION aND pOssIBly pErsONal INJury rEsulTINg frOm 
uNNECEssary swITChINg Of CONNECTED EQuIpmENT. ThIs 
kIND Of TEsTINg shOulD ONly BE CONDuCTED IN ThE “TEsT,” 
“DIsCONNECTED” Or “rEmOVE” CEll pOsITIONs.

4.6  Digitrip OPTIM 750

Digitrip OPTIM 750 Trip Units provide true rms sensing and 
utilize a fixed interchangeable rating plug to establish the 
continuous trip rating of the circuit breaker. Rating plugs are 
interlocked to prevent use between different circuit breaker 
types. 

Precise system coordination is provided by the following 
time-current curve shaping adjustments: 

1.  Long delay pickup
2. Long delay time with selectable I

2

t or I

4

t curve 

  shaping
3. Short delay pickup
4. Short delay time with selectable flat or I

2

t curve 

  shaping
5. Instantaneous pickup
6. Ground fault pickup
7.  Ground fault time with selectable flat or I

2

t curve shaping

The trip units also have a selectable powered/unpowered 
thermal memory to provide protection against cumulative 
overheating should a number of overload conditions occur in 
quick succession.

The trip unit information system utilizes battery backup LEDs 
to indicate the trip mode following an automatic trip opera-
tion. The LEDs are complemented by trip event informa-
tion that is stored in memory after a trip condition. This trip 
information can then be accessed via the OPTIMizer Hand 
Held Programmer, the Breaker Interface Module, or over the 
IMPACC System. A trip reset pushbutton is provided on the 
trip unit to turn off the LED indication after an automatic trip. 
The battery status is also LED indicated through the use of a 
pushbutton. 

Selectable early warning alarms, capable of being indicated 
locally and remotely, are provided to help keep a system 
operating and productive. 

All OPTIM Trip Units are capable of monitoring the following 
data:

1.   Steady-State value of phase, neutral, and ground currents
2. Minimum and maximum current values
3. Average demand current
4. Cause of trip (Long Delay, Short Delay, Instantaneous or 

Ground Fault)

5. High load current alarm
6. Magnitude of fault current responsible for an automatic 

trip operation

Monitoring and Control

Trip units are capable of two way communication via a 
network twisted pair for remote monitoring and control. The 
circuit breaker, through the trip unit, is able to respond to 
open and close commands via the communication network. 
To close the breaker, an electrical operator or spring release 
option is required.

Effective July 2010

 

Instructional Leaflet

 IL8700C39-04

10

eaTOn CORPORaTIOn

 www.eaton.com

Summary of Contents for Digitrip RMS Series

Page 1: ...Potential Transformer Module 15 6 0 Testing 15 6 1 Functional Field Testing 15 6 1 1 Secondary Injection Testing 15 6 2 Performance Testing for Ground Fault Trip Units 18 6 2 1 Code Requirements 18 6...

Page 2: ...ing every application or circumstance which may arise If any questions arise contact Eaton for further information or instructions 1 0 Supplementary Information The instructions contained in this book...

Page 3: ...ies as the OPTIMizer Hand Held Programmer plus energy monitoring local remote indi cation and communications capabilities except that only the Hand Held Programmer can establish trip unit addresses Se...

Page 4: ...Effective July 2010 Instructional Leaflet IL8700C39 04 Figure 2a Typical Digitrip RMSTrip Unit Display Panels Figure 2b Typical Digitrip OPTIMTrip Unit Display Panels 4 eaton corporation www eaton com...

Page 5: ...ted using secondary currents provided by an Amptector Trip Unit test kit as illustrated in I L 33 791 Detailed instructions for testing trip units are given in the individual trip unit instruction lea...

Page 6: ...test receptacles for external field testing mounted in the breaker Figures 4 and 5 4 2 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit described in I L 29...

Page 7: ...gnal Contact High Load Alarm X X X X X Long Delay Trip X X X X X Short Circuit Trip X X X X X Ground Fault Trip o o o o o Ground Alarm Integral Test Provisions X X X X Trip Unit Status Indication LED...

Page 8: ...l Ground Fault GNDT l o l o Long Delay LDT l l Overtemperature TEMP l l External Trip EXTT l l Long Time Delay Pickup LDPU l l Over Range Trip ORNG l l Information Normal NORM l l Protection Settings...

Page 9: ...ting a Potential Transformer Module and a Power Relay Module mounted as shown in Figures 4 and 5 The Digitrip RMS 810 Trip Unit performs all the functions of the Digitrip RMS 610 Trip Unit with the ad...

Page 10: ...ze a fixed interchangeable rating plug to establish the continuous trip rating of the circuit breaker Rating plugs are interlocked to prevent use between different circuit breaker types Precise system...

Page 11: ...6 for OPTIM 750 In addition OPTIM 1050 Trip Units are capable of pro viding data on power quality and permit energy monitoring Energy Monitoring 1 Peak demand kW 2 Present demand kW 3 Forward energy...

Page 12: ...power required 5 2 Digitrip Trip Assembly The basic Digitrip Trip Assembly as shown in Figures 4 and 5 includes the following which could vary slightly depending upon the exact model of the Digitrip T...

Page 13: ...l sensing scheme which vectorially sums the outputs of the individual phase current sensors As long as the vecto rial sum is zero then no ground fault exists If the system neutral is grounded and a ne...

Page 14: ...t signal will be equivalent to a single BYZ sensor The BYZ current sensor styles shown in Figure 7 are avail able for all previously mentioned applications When either style sensor is used the ground...

Page 15: ...FORMER MODULE DISCONNECT PLUG IS CONNECTED DEATH OR SEVERE PERSONAL INJURY MAY RESULT AND THE POTENTIAL TRANSFORMER MODULE AND TRIP UNIT WILL BE DAMAGED REMOVE THE PTM DISCONNECT PLUG PRIOR TO PERFORM...

Page 16: ...AMPTECTORTEST KIT STYLES 140D481G02R 140D481G02RR OR 140D481G03 IN CONJUNCTION WITH A DIGITRIP ADAPTER STYLE 8779C02G01 SHOULD BE USED UNMODIFIED AMPTECTORTEST KIT STYLES 140D481G01 AND 140D481G02 SH...

Page 17: ...harge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Results Breaker Number Figure 9 Typical PerformanceTest Record Form Effe...

Page 18: ...ource apply a test current of 125 of the Digitrip Ground Fault Trip Unit pickup setting through one phase of the circuit breaker as shown in Figure 8a This should cause the breaker to trip in less tha...

Page 19: ...Curves for Types DSII and DSLII Circuit Breakers with Digitrip OPTIM 750 and 1050 Trip Units SC 6275 95 Typical Long Delay I2 t Short Delay I2 t Types DSII and DSLII rated up to 1200A SC 6276 95 Typic...

Page 20: ...______ By____________________________ Figure 10 TypicalTrip Function Record Digitrip Automatic trip operation record Circuit No Address Breaker Shop Order References ________________ _________________...

Page 21: ...Effective July 2010 Instructional Leaflet IL8700C39 04 21 eaton corporation www eaton com...

Page 22: ...Effective July 2010 Instructional Leaflet IL8700C39 04 22 eaton corporation www eaton com...

Page 23: ...Effective July 2010 Instructional Leaflet IL8700C39 04 23 eaton corporation www eaton com...

Page 24: ...icies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR...

Reviews: