Instruction Leaflet IL 33-LGH-3
Effective September 2010
Digitrip Retrofit System for the ITE
LG-3000 (Frameless) Circuit Breaker
G. Attach the appropriate label for the Breaker in a
clearly visible position. Four (4) labels are
included with the CPT, one (1) for 575 Volt, one
(1) for 480 Volt, one (1) for 240 Volt, and one
(1) for 208 Volt systems.
H. The HV Wires will be cut to length and
connected to the Breaker later in the Retrofit
Process. Temporarily route the HV Wires out
the front of the Breaker so they do not interfere
with the Retrofit Process.
Step 5:
Installing the Sensors
A. For Kits Supplied with a Breaker Mounted CPT
Only. Install the grommet in the hole to the left
of center of the Sensor Mounting Bracket.
B. Align the Sensors, as shown, with the Sensor
Mounting Bracket. Note that the Sensor
Terminals are positioned in the cut-outs in the
Mounting Bracket and the Sensor Labels face
outward.
208V
CONTROL POWER TRANSF. TAPS
H1–H4=480V
H2–H4=240V
H3–H4=208V
WARNING
THIS BREAKER CONTAINS A 50VA
CONTROL POWER TRANSFORMER
FOR TRIP UNIT DISPLAY. IF BREAKER
IS USED ON A LINE VOLTAGE OTHER
THAN SHOWN. THE CPT TAPS MUST
BE CHANGED BEFORE ENERGIZING.
FAILURE TO DO SO WILL RESULT IN
DAMAGE TO THE TRIP UNIT AND / OR
CONTROL POWER TRANSFORMER
NP# 9A10039H04
240V
CONTROL POWER TRANSF. TAPS
H1–H4=480V H2–H4=240V
H3–H4=208V
WARNING
THIS BREAKER CONTAINS A 50VA
CONTROL POWER TRANSFORMER
FOR TRIP UNIT DISPLAY. IF BREAKER
IS USED ON A LINE VOLTAGE OTHER
THAN SHOWN. THE CPT TAPS MUST
BE CHANGED BEFORE ENERGIZING.
FAILURE TO DO SO WILL RESULT IN
DAMAGE TO THE TRIP UNIT AND / OR
CONTROL POWER TRANSFORMER
NP# 9A10039H03
480V
CONTROL POWER TRANSF. TAPS
H1–H4=480V H2–H4=240V
H3–H4=208V
WARNING
THIS BREAKER CONTAINS A 50VA
CONTROL POWER TRANSFORMER
FOR TRIP UNIT DISPLAY. IF BREAKER
IS USED ON A LINE VOLTAGE OTHER
THAN SHOWN. THE CPT TAPS MUST
BE CHANGED BEFORE ENERGIZING.
FAILURE TO DO SO WILL RESULT IN
DAMAGE TO THE TRIP UNIT AND / OR
CONTROL POWER TRANSFORMER
NP# 9A10039H02
575V
CONTROL POWER TRANSF. TAPS
H1–H4=575V
WARNING
THIS BREAKER CONTAINS A 50VA
CONTROL POWER TRANSFORMER
FOR TRIP UNIT DISPLAY. IF BREAKER
IS USED ON A LINE VOLTAGE OTHER
THAN SHOWN. THE CPT TAPS MUST
BE CHANGED BEFORE ENERGIZING.
FAILURE TO DO SO WILL RESULT IN
DAMAGE TO THE TRIP UNIT AND / OR
CONTROL POWER TRANSFORMER
NP# 9A10039H01