Table 2. Torque Values for General Mounting and Screw Size
Conversion.
Decimal Size (in)
Standard Size
Torque (in-lbs)
Torque (ft-lbs)
.112
4.40
10
0.8
.138
6.32
18
1.5
.164
8.32
36
3.0
.190
10.32
46
3.8
.250
1/4-20
100
8.3
.312
5/16-18
206
17.2
.375
3/8-16
356
29.7
.438
7/16-14
572
47.7
.500
1/2-13
856
71.3
.
Table 3. Torque Values for Copper BUS Connectors.
Decimal Size (in)
Standard Size
Torque (in-lbs)
Torque (ft-lbs)
.250
1/4-20
60
5
.312
5/16-18
144
12
.375
3/8-16
240
20
.500
1/2-13
600